Table 3.2 Input Fuses for Models 4A0930 and 4A1200VoltageClass ModelSelection Input Fuse (Example)Input Voltage Current Pre-arcI2t (A2s) Model Manufacturer Rating Pre-arcI2t (A2s)Three-Phase400 VClass4A0930480 V 1500 A 140000 to3100000CS5F-1200 Fuji Electric AC500 V, 1200 A 2760004A0930 with12-pulserectificationFWH-1200A Bussman AC500 V, 1200 A –FWH-1000A Bussman AC500 V, 1000 A –4A1200480 V 1500 A 320000 to3100000CS5F-1500 Fuji Electric AC500 V, 1500 A 3510004A1200 with12-pulserectificationFWH-1600A Bussman AC500 V, 1600 A –FWH-1200A Bussman AC500 V, 1200 A –u Protecting Main Circuit Terminalsn Insulation Caps or SleevesUse insulation caps or sleeves when wiring the drive with crimp terminals. Take particular care to ensure that the wiring doesnot touch nearby terminals or the surrounding case.n Insulation BarrierInsulation barriers are packaged with drive models 4A0414 through 4A1200 to provide added protection between terminals.Yaskawa recommends using the provided insulation barriers to ensure proper wiring. Refer to Figure 3.27 for instructions onplacement of the insulation barriers.Insulation BarrierFigure 3.27 Installing Insulation Barriers3.8 Main Circuit Wiring84 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual