Setting 0: DisabledA Run command is not accepted while the digital operator is in Programming Mode.Setting 1: EnabledA Run command is accepted in any digital operator mode.Setting 2: Prohibit programming during runIt is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot bedisplayed during Run.n b1-11: Drive Delay Time SettingIf a time is set to b1-11, the drive will delay executing a Run command until the set time has expired. During Drive DelayTime execution, the digital operator keypad will display “WrUn”. Both Alarm and Run indicators will blink while the drivewaits to execute the Run command.No. Parameter Name Setting Range Defaultb1-11 Drive Delay Time Setting 0 to 600 s 0n b1-14: Phase Order SelectionSets the phase order for drive output terminals U/T1, V/T2, and W/T3.Switching motor phases will reverse the direction of the motor.No. Parameter Name Setting Range Defaultb1-14 Phase Order Selection 0, 1 0n b1-15: Frequency Reference Selection 2Enabled when H1-oo = 2 and the terminal is closed. Refer to Setting 2: External Reference 1/2 Selection on page 207 andRefer to b1-02: Run Command Selection 1 on page 148 for details.No. Parameter Name Setting Range Defaultb1-15 Frequency Reference Selection 2 0 to 4 0n b1-16: Run Command Selection 2Enabled when H1-oo = 2 and the terminal is closed. Refer to Setting 2: External Reference 1/2 Selection on page 207 andRefer to b1-01: Frequency Reference Selection 1 on page 147 for details.No. Parameter Name Setting Range Defaultb1-16 Run Command Selection 2 0 to 3 0n b1-17: Run Command at Power UpDetermines whether an external Run command that is active during power up will start the drive.No. Parameter Name Setting Range Defaultb1-17 Run Command at Power Up 0, 1 1Setting 0: DisregardedA new Run command must be issued after power up. Cycle the Run command to start the drive.Note: For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is issued atpower up, the RUN indicator LED will flash quickly.Setting 1: AllowedThe motor will start immediately after a power up if a Run command is already enabled.WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will beginrotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior topowering up the drive. Failure to comply may cause serious injury.u b2: DC Injection Braking and Short Circuit BrakingThese parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.5.2 b: Application152 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual