Using the display panel Azbil Corporation4-46 Model MGG10C/14C - MagneW FLEX+/PLUS+ ConverterPulse weightThis function is used to set the pulse weight value and pulse weight unit.Pulse weight should be set so that pulse frequency indicated on the display is between0.00006 and 3000Hz.When changing the pulse weight with the dual range, use the wider range.Step Screen Procedure(English) (Japanese)1 PLS 27.780 HzSCL 100.00 l/p27.780 Hz100.00 l/pEnter ENGINEERING MODE(see page 4-23). Use the orkey to cycle through the screensuntil the PLS (pulse weight)screen appears.2 PLS 27.780 HzSCL 100.00 l/p27.780 Hz100.00 l/pTouch the key until the cursoris at the pulse weight value to bechanged.Default setting: 100.00 cm3 /P.3 PLS 13.890 HzSCL 200.00 l/p13.890 Hz200.00 l/pTouch the or key to changethe value.4 PLS 13.890 HzSCL 200.00 l/p13.890 Hz200.00 l/pUse the key to move thecursor to the pulse weight unit.5 PLS 13.890 HzSCL 200.00 cm /p313.890 Hz200.00 cm /p3Touch the or key to changethe pulse weight unit.CAUTIONPulse weight units must matchspan units.6 PLS 13.890 HzSCL 200.00 cm /p313.890 Hz200.00 cm /p3Touch the key until the cursoris back at the mode indicator.