Azbil Corporation Using the display panelModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 4-61Manual spike cut functionThis function eliminates steep noise spikes (spike noise) in the flow rate. The manualspike cut function enables to set parameters, spike cut level and spike cut time to bestmeet the customers application.Default settingSpike cut time 0Spike cut level 1.0Setting rangeSpike cut time: 00.0 to 99.9sSpike cut level: 1.0 to 99.9%Step Screen Procedure(English) (Japanese)1SPIKE CUTTIME 00.0 SEC&SPIKE CUTLEVEL 00.0 %&00.0 SEC&00.0 %&Enter the ADVANCED Mode.(See page 4-23).Use theor key to cycle through thescreens until SPIKE CUT TIMEor SPIKE CUT LEVEL screenappears.2SPIKE CUTTIME 01.0 SEC&SPIKE CUTLEVEL 10.0 %&01.0 SEC&10.0 %&Touch the key to movethe cursor to the value to bechanged. Touch the or keyto set a desired value.3Touch the MODE key to returnto the MEASURING MODEand save the data.