Azbil Corporation Using the display panelModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 4-39The high/low limit alarm can be set to ST.OUT1 and the range switching outputto ST.OUT2.B: Range switching output and counter preset status output (2-contact output)The range switching output can be set to ST.OUT1 and the preset status output toST.OUT2.C: Range switching output and (self-check result output or empty detection)(2-contact output)The range switching output can be set to ST.OUT1 and the output when either aself-check result or empty detection abnormality occurs to ST.OUT2.D: Alarm contact output and counter preset status output (2-contact output)The alarm contact output can be set to ST.OUT1 and the counter preset statusoutput to ST.OUT2.E: 2-stage flow rate alarm outputThe high/low limit alarm can be set to ST.OUT1 and the 2-stage high limit alarmor 2-stage low limit alarm to ST.OUT2.LL L H HHST.OUT1ST.OUT2Figure 4-4 2-stage flow rate alarm outputF: Counter preset status output and self-check result output (2-contact output)The counter preset status output can be set to ST.OUT1 and the self-check resultoutput can be set to ST.OUT2.G: Counter preset status output and empty detection functionThe counter preset status output can be set to ST.OUT1 and empty detectionfunction can be set to ST.OUT2.H: Range switching output and High/low limit alarm outputThe range switching output can be set to ST.OUT1 and High/low limit alarm canbe set to ST.OUT2.I: Self-check result output and empty detection functionThe self-check result can be set to ST.OUT1 and empty detection function can beset to ST.OUT2.J: Self-check result output and High/low limit alarmThe self-check result can be set to ST.OUT1 and the high/low alarm can be set toST.OUT2.K: Empty detection function and High/low limit alarmThe empty detection function can be set to ST.OUT1 and the high/low limit alarmcan be set to ST.OUT2.