Using the display panel Azbil Corporation4-50 Model MGG10C/14C - MagneW FLEX+/PLUS+ ConverterSetting a 2-stage flow rate alarmThe first alarm will be output when the instantaneous percent flow rate exceeds thepreset first high or low limit. The second alarm will be output when the flow rateexceeds the second high or low limits.ImportantThis function can be used when the 2-stage high/low limit alarm is selected in thecontact output function.Default settingHI-ALM1, HI-ALM2 +115% LO-ALM1, LO-ALM2 -115%Setting rangeHI-ALM1, HI-ALM2 -115 to +115% LO-ALM1, LO-ALM2 -115 to +115%Step Screen Procedure(English) (Japanese)1 HI-ALM1 + 100 %LO-ALM1 - 100 %HI 1 + 100 %LO 1 - 100 %Open the 2-stage high/lowlimit alarm setup screen byfollowing the steps to enter theengineering mode.2 HI-ALM1 + 100 %LO-ALM1 - 100 %HI 1 + 100 %LO 1 - 100 %Use the key to move thecursor to the desired digits.3 HI-ALM1 + 020 %LO-ALM1 + 010 %HI 1 + 020 %LO 1 + 010 %Use the and keys tochange the numbers.4 HI-ALM1 + 020 %LO-ALM1 + 010 %HI 1 + 020 %LO 1 + 010 %Touch the key to move thecursor to the “#”.5 HI-ALM2 + 100 %LO-ALM2 - 100 %HI 2 + 100 %LO 2 - 100 %Touch the key to set the2-stage high limit alarm in thesame way.6 HI-ALM2 + 100 %LO-ALM2 - 100 %HI 2 + 100 %LO 2 - 100 %Use the key to move thecursor to the desired digits.7 HI-ALM2 +090 %HI-ALM2 - 20 %HI 2 + 090 %LO 2 - 20 %Use the and keys tochange the numbers.