Introduction Azbil Corporation1-8 Model MGG10C/14C - MagneW FLEX+/PLUS+ ConverterSystem Configuration for Digital Output (DE Output)System configurationFigure 1-5 shows a system configuration in which the flow rate measured by theunit, the database in the unit, and self-diagnostics are output using the DE (DigitalEnhancement) protocol (rules for digital signal communication).In this system, the DE protocol-based digital signal transmitted from the unit isoutput to the control system after conversion to an analog signal at the smart protocolconverter (SPC). Or, the digital signal is directly transmitted to the control system, ifit is capable of receiving the DE protocol-based signal directly.AC or DCpowersupplyDeviceAC or DCpowersupplyDeviceControlsystemSHLSFCSFCPM100,PM300,orA-MCSPCFigure 1-6 System configuration for digital outputSmart Electromagnetic Flowmeter (device)Measures flow rate and outputs the instantaneous flow rate and unit self-diagnosticsusing a digital signal.Smart protocol converter (SPC)Converts the DE protocol-based digital signal into a 4 to 20 mA or 1 to 5 V DCanalog signal for output.Smart handy loader (SHL)Used to change the SPC settings.Smart communicator (SFC)• Used to communicate with the device to read data and change the device settings.PM100• Simultaneously executes such functions as process control on the UCN, regulatorycontrol, sequencing, calculation, and process input/output.