Azbil Corporation Maintenance and TroubleshootingModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 5-3Analog output checkThe analog output can be checked by using the electromagnetic flowmeter as aconstant-current generator.Default settingExisting analog outputSetting range000.0 to 115.0%Step Screen Procedure(English) (Japanese)1 > OUTPUT CHECKI. OUT 000.0 %>4 - 20 000.0 %Enter MAINTENANCE MODE(see page 4-24). Use the orkey to cycle through screenuntil “OUTPUT CHECK”screen appears. Touch thekey once to move the cursorto “OFF”. Touch the key toswitch the OFF screen to ONscreen.2 > OUTPUT CHECKI. OUT 000.0 %>4 - 20 000.0 %Touch the key to move thecursor at the percent value to bechecked.3 > OUTPUT CHECKI. OUT 100.0 %>4 - 20 100.0 %Use the or key to set thedesired value. In this example,the analog output is set as 100%,i.e. 20mA.4 > OUTPUT CHECKI. OUT 100.0 %> 4 - 20 100.0 %Touch the key to move thecursor to “>”.5Use the or key to moveother screen. Then the analogoutput is back to the valueaccording to the measured flowrate.~ Note If no operation is done for ten minutes, the output check mode automatically finishesand return to the Measuring mode.