Azbil Corporation InstallationModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 2-19Setting write protectionWrite protection settings allow you to control the level at which data confirmationand manipulation are possible. The system has four modes:Basic setup mode - used to run the flowmeter on a day-to-day basis.Engineering mode - used by those who are responsible for flowmeter configuration.Maintenance mode - used when system maintenance is required.Advanced mode - used to apply some specific noise immunity functions, and otheradvanced functions.Write protection settings are changed by setting the switch positions of the writeprotection switch on the main card in the converter. When the flowmeter is shipped,settings can be made in any mode (Level 0). The following table shows the writeprotect levels available by resetting the switch:Table 2-7 Write Protection LevelsLevelBasic setup/EngineeringmodeAdvancedmodeMaintenancemode Remarks0 a a a Default setting1 a a r2 a – r3 – – ra - Both data confirmation and manipulation are possible.– - Only data confirmation is possible.r - Neither data confirmation nor manipulation are possible.