Azbil Corporation InstallationModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 2-15Wiring cableSelecting the cableThe recommended wiring cable is a 600V vinyl sheath electrical wire CVV (JIS C3401) with a conductor section of 2 mm2(0.0031 inch2), or a twisted cable with anequivalent or higher capacity.Shielded wire is recommended for wiring at locations subject to electromagneticnoise interference.Select a sheath material suitable for the cable installation environment (considerambient temperature, corrosive gas, corrosive fluid, etc.)Run the cable into the terminal block through the conduit connection (G1/2 internalthread, CM20 external thread, Pg13.5 or 1/2NPT internal thread).An outer diameter off11(0.433 inch) is optimum. (The applicable range of cableouter diameters isf10(0.394 inch) -f12(0.4724 inch).)A crimp terminal (M4 screw) with an insulation sleeve is recommended for theterminal connections.The maximum length of the wiring cable is 1500 m(4921 ft). However, the maximumlength between converter and detector is 300 m(984 ft).Wiring the cableWhen wiring the cable between this product and the control equipment, the followingprecautions must be observed.~ Note • Run the wiring away from equipment that may generate noise, such as high-capacity transformers, motors, or power supplies. DO NOT install the cable in thesame tray or duct as other power cables. Output errors may result.• For water proofing and damage prevention of the wire, we recommend cablingwork using conduits and ducts. Use a water proof cable gland.