Azbil Corporation Using the display panelModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 4-49Setting high and low limit alarmsAn alarm is output when the instantaneous percent flow rate exceeds the preset highand low limits.ImportantThis function can be used when the high/low limit alarm is selected in the contactoutput function.Default settingHI-ALM +115%, LO-ALM -115%Setting rangeHI-ALM -115 to +115%, LO-ALM -115 to +115%Step Screen Procedure(English) (Japanese)1 HI-ALM +100 %LO-ALM - 100 %HI +100 %LO - 100 %Open the high and low limitalarm setup screen by followingthe steps to enter the engineeringmode.2 HI-ALM +100 %LO-ALM - 100 %HI +100 %LO - 100 %Use the key to move thecursor to desired digit.3 HI-ALM +080 %LO-ALM - 100 %HI +080 %LO - 100 %Use the and keys tochange the numbers.4 HI-ALM +080 %LO-ALM - 100 %HI +080 %LO - 100 %Touch the key to move thecursor to the “#”.Make sure to set so that HI-ALM>LO-ALM.