Azbil Corporation Using the display panelModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 4-53Selecting fail-safe mode for the pulse outputThis function is used to determine the pulse output direction when theelectromagnetic flowmeter detects a critical status condition.CAUTIONThe fail-safe mode is very important for overall safety of the control process.Choose the fail-safe direction carefully, as equipment damage can result from awrong choice.Default setting“LOW”Setting range“LOW” Outputs no pulse“HOLD” Holds the pulse to the value obtained just before the critical statuscondition occurred.Step Screen Procedure(English) (Japanese)1 FAIL SAFE MODEP.OUT LOW LOWOpen the fail-safe mode forthe pulse output screen byfollowing the steps to enter theengineering mode.2 FAIL SAFE MODEP.OUT LOW LOWTouch the key.3 FAIL SAFE MODEP.OUT HOLD HOLDUse the or key todetermine the fail-safe direction.4 FAIL SAFE MODEP.OUT HOLD HOLDTouch the key to move thecursor to the “#”.