Azbil Corporation Using the display panelModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 4-31Normal direction automatic dual rangeThis function has two ranges: wide and narrow. When the narrow range measurementexceeds 100%, the unit automatically changes to the wide range.This function should be used in combination with the wide/narrow range distinctionoutput contact. Hysteresis setting is available when dual range is selected.j When AUTO is selected for an analog outputRange No.1 4 to 20 mA DCRange No.2 4 to 20 mA DCk When WIDE is selected for an analog output4 to 20 mA DC is output according to either range No.1 or range No.2, whicheverhas the wider range.When there is a pulse outputThe pulse weight is the same for both ranges No.1 and No.2.Contact outputAt shipment, the contact output status of the distinction status signal for rangesNo.1 and No.2 is as follows.Range No.1: ClosedRange No.2: OpenReverse setting is also possible.InputOutput20 mA4 mA a. c.b. d.100%0%Figure 4-2 Normal direction automatic dual range(Example)j AUTO rangeRange No.1 (narrow range): Outputs 4 to 20 mA for 0 to 10 m3 /h (a-b).Range No.2 (wide range): Outputs 4 to 20 mA for 0 to 40 m3/h (a-d)k WIDE rangeRange No.1 (narrow range): Outputs 4 to 8 mA for 0 to 10 m3 /h (a-c).Range No.2 (wide range): Outputs 8 to 20 mA for 10 to 40 m3/h (c-d).