Maintenance and Troubleshooting Azbil Corporation5-4 Model MGG10C/14C - MagneW FLEX+/PLUS+ ConverterPulse output checkThe pulse output can be checked by using the electromagnetic flowmeter as a pulsegenerator.Default settingExisting measured valueSetting range000.0 to 115.0%Step Screen Procedure(English) (Japanese)1 > OUTPUT CHECKP. OUT 000.0 %>100.0 %Enter MAINTENANCE MODE(see page 4-24). Use the orkey to cycle through screenuntil “OUTPUT CHECKI.OUT” screen appears. Touchthe key once to move thecursor to “OFF”. Touch thekey to switch the OFF screento ON screen. Touch the keyonce to move to “OUTPUT P.OUT” screen.2 > OUTPUT CHECKP. OUT 000.0 %>000.0 %Touch the key to move thecursor at the percent value to bechecked.3 > OUTPUT CHECKP. OUT 100.0 %>100.0 %Use the or key to set thedesired value. In this example,the pulse equivalent to the 100%flow rate is output.4 > OUTPUT CHECKP. OUT 100.0 %>100.0 %Touch the key to move thecursor to “>”.5Use the or key to moveother screen. Then the pulseoutput is back to the valueaccording to the measured flowrate.~ Note If no operation is done for ten minutes, the output check mode finishes automaticallyand return to the Measuring mode.