Using the display panel Azbil Corporation4-56 Model MGG10C/14C - MagneW FLEX+/PLUS+ ConverterDamping time constantThe damping time constant removes minute fluctuations when transmitting themeasured flow rate to the control equipment. Check the amplitude of fluctuation inflow output and set the damping time constant to an appropriate value. The new valuebecomes effective as soon as it is enteredDefault setting3.0 second.Setting range0.1 to 199.9 seconds.(0.0 to 199.9 seconds for “Fast Response Option for Short Run Batch Process.”)Step Screen Procedure(English) (Japanese)7 MODE ENTERADVANCEDEnter the ADVANCED mode.(See page 4-23).8 DAMPING003.0s& &Use the Touch or key tocycle through the screens untilthe damping screen appears.9 DAMPING003.0s& &Touch the key until thecursor is at the value to bechanged. (in the example, thekey is touched three times.)10 DAMPING010.0s& &Use or key to changethe numeric value. Touch andholding either key quicklyincrements or decrements thevalues.11 DAMPING010.0s& &Touch the key until thecursor is back at the modeindicator. Touch the MODEkey and hold for three secondsto return to MEASUREMENTMODE to save the DampingTime Value.