Installation Azbil Corporation2-18 Model MGG10C/14C - MagneW FLEX+/PLUS+ ConverterContact input wiringEither a semi conductive contact or a no-voltage contact can be used as the contactinput.The contact input terminals are not available when a 2-contact output model has beenselected.Required specifications for thesemi - conductive contact.OFF: Withstand voltage 30V min.Leak current 0.1mA max.ON : Saturation voltage 3V max.ON current 15mA max.Required specifications forNo-voltage contact.OPEN: Resistance 100k min.CLOSE : Resistance 400 max.STATUS INSTATUS INSTATUS INSTATUS IN24V24VFigure 2-18 Wiring diagram for contact inputContact output wiringPay close attention to voltage and polarity when wiring for an open collector output.Protective diodeLoadExternalpower supply30V max.Avoid this polarityFigure 2-19 Wiring diagram for contact output~ Note Check and confirm that the polarity of the wiring is correct. Incorrect polarity maycause damage to the equipment.Use an external power supply that meets the voltage and capacity specifications.