Installation Azbil Corporation2-10 Model MGG10C/14C - MagneW FLEX+/PLUS+ ConverterRemote wiring - 2 (2-contact input)To wire a remote system, the following cables are required:• Signal cable - see page 2-12• Excitation cable - see page 2-12• Analog output cable - see page 2-16• Pulse output cable - see page 2-17• Contact input/output cable - see page 2-17The following pages provide information on selecting the correct cables and wiringthe system. A diagram of the terminal block for a remote system is shown below.2-contact inputACPOWERE STATUS IN 1 STATUS IN 2+ - + -+ - + -X YPOWER ACL NSB SA C ABI. OUTP. OUTE STATUS IN 1 STATUS IN 2+ - + -+ - + -X YPOWER ACL NSB SA C ABI. OUTP. OUTFigure 2-8 Remote converter terminal blockTable 2-5 Remote converter terminal descriptions (2-contact input)Symbol DescriptionAFlow rate signal inputBCSASBI. OUT + Analog output–P. OUT + Pulse output–STATUS IN 1 + Contact input 1–STATUS IN 2 + Contact input 2–X ExcitationYE Not usedGrounding (grounding resistance must be <100 W)~ Note In case of DC24V and DC110V power supply, the symbol of the “L” and “N” of thepower supply become “+” and “–”.