Azbil Corporation Using the display panelModel MGG10C/14C - MagneW FLEX+/PLUS+ Converter 4-63Setting the drop-outA drop out is set to prevent incorrect integration of the flow rate. Pulse counting willpause when the flow rate is at the preset percentage of the set range.Default setting2%Setting range0 - 10%Step Screen Procedure(English) (Japanese)1 DROP OUT02 %&02 %&Enter ADVANCED MODE (seepage 4-23). Use the orkey to cycle through the screensuntil the DROPOUT screenappears.2 DROP OUT02 %&02 %& Touch the key.3 DROP OUT05 %&05 %& Use the and keys tochange the numbers.4 DROP OUT05 %&05 %& Touch the key to move thecursor to the “&”.5Touch the MODE key return tothe MEASURING MODE andsave the data.