Chapter 6: Using the Web Interface246Configuring Environmental Sensors or ActuatorsYou can change the default name to easily identify the managed sensoror actuator, and describe its location with X, Y and Z coordinates.To configure environmental sensors or actuators:1. Click Peripheral Devices in the left pane.2. Select the sensor or actuator that you want to configure.3. Click Setup in the right pane. The "Setup of peripheral device number> ()" dialog appears, where isits serial number and is its type.For example, Setup of peripheral device AEI7A00022 (Temperature).4. Configure available fields properly.Fields DescriptionName Assign a name for identification.Description Type any descriptive text as needed.Location (X, Y andZ)Describe the sensor's or actuator's location by assigning alphanumeric values to theX, Y and Z coordinates. See Describing the Sensor's or Actuator's Location (onpage 248).When the term "Rack Units" appears inside the parentheses in the Z location field,indicating that the Z coordinate format is set to Rack Units, you must type an integernumber. See Setting the Z Coordinate Format (on page 247).Binary SensorSubtypeThis field is available only when the selected sensor is a contact closure sensor.Select one of the following sensor types: Contact: The detector/switch is designed to detect the door lock or dooropen/closed status. Smoke Detection: The detector/switch is designed to detect the appearanceof smoke. Water Detection: The detector/switch is designed to detect the appearanceof water on the floor. Vibration: The detector/switch is designed to detect the vibration in the floor.Alarmed to NormalDelayThis field is available only when the selected sensor is the DX-PIR presencedetector.It determines the wait time before the EMX announces that the presence detectorreturns to the normal state after it is back to normal.Type both the time and measurement units in this field. For example, type '30 s' for30 seconds, or '2 min' for 2 minutes.