Chapter 6: Using the Web Interface285Managing Schneider Electric PowerLogic PM710Configuring the PM710 and Configuring Threshold SettingsAll settings are configured on a per port basis. If you disconnect aPM710 from one EMX port and connect it to another, you mustreconfigure the settings. However, if you disconnect a PM710 from a portand then plug it back in to the same port, the already configured settingsstill apply.Note: EMX2-888 does not support the PowerLogic PM710.To configure the PM710:1. Connect the PM710 sensor to EMX2-111 if it is not alreadyconnected. See Connecting the Schneider Electric PowerLogicPM710 (on page 63).2. Pin the auxiliary port to the PM710.3. If the Auxiliary Ports folder is not expanded, expand it to show alldevices connected to the RS-485 ports.4. Click the desired sensor in the EMX Explorer pane. The pagespecific to that sensor opens in the right pane.5. Click Setup in the Settings section. The Setup dialog opens.6. Enter a name for the sensor in the Name field.7. Leave the device address, line speed and parity as is so it matchesthe PM710 settings.8. Click OK.9. Configure the threshold settings if needed. Click on Thresholds atthe bottom right of the Sensors section or Power Quality section ofthe page. The Thresholds dialog opens and displays the sensorreadings gathered by EMX.10. Select a reading and then click Edit, or double click on a reading toopen its corresponding Threshold dialog.11. Check the checkboxes next to the readings you want to setthresholds for, then edit the thresholds as needed. Click OK to savethe changes.