Chapter 8: Using the Command Line Interface414Example - Default Upper Thresholds for TemperatureIt is assumed that your preferred measurement unit for temperature isset to degrees Celsius. Then the following command sets the defaultUpper Warning threshold to 20and Upper Critical threshold to 24for all temperature sensors.config:#defaultThresholds temperature upperWarning 20upperCritical 24Environmental Sensor Threshold Configuration CommandsYou can use the sensor threshold configuration commands to set thethreshold, hysteresis and assertion timeout values for any environmentalsensor.It is permitted to assign a new value to the threshold at any timeregardless of whether the threshold has been enabled.Threshold Configuration Commands for a SensorA sensor threshold configuration command for environmental sensorsbegins withsensor externalsensor.You can configure various environmental sensor threshold settings at atime by combining multiple commands. SeeMulti-Command Syntax(on page 431).Set the Upper Critical threshold for an environmental sensor:config:#sensor externalsensor upperCritical Set the Upper Warning threshold for an environmental sensor:config:#sensor externalsensor upperWarning Set the Lower Critical threshold for an environmental sensor:config:#sensor externalsensor lowerCritical Set the Lower Warning threshold for an environmental sensor: