Chapter 8: Using the Command Line Interface411Using Default ThresholdsThis command determines whether default thresholds, including thedeassertion hysteresis and assertion timeout, are applied to a specificenvironmental sensor.config:#externalsensor useDefaultThresholds Variables: is the ID number of the environmental sensor that you want toconfigure. The ID number is available in the EMX web interface orusing the command "show externalsensors " in the CLI. It isan integer between 1 and 32.trueorfalse.OptionDescriptiontrueDefault thresholds are selected as the thresholdoption for the specified sensor.falseSensor-specific thresholds are selected as thethreshold option for the specified sensor.Setting the Alarmed to Normal Delay for DX-PIRThis command determines the value of the Alarmed to Normal Delaysetting for a DX-PIR presence detector.config:#externalsensor alarmedToNormalDelay Variables: is the ID number of the environmental sensor that you want toconfigure. The ID number is available in the EMX web interface orusing the command "show externalsensors " in the CLI. It isan integer between 1 and 32.ExamplesThis section illustrates several environmental sensor configurationexamples.