4 PKE-SWD-32, interface for motor-starter combination with PKE12/324.9 Programming118 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com4.9.3 Data profilesThe quantity of cyclical input data of the PKE-SWD-32 can be adapted to theapplication with different data profiles of the module. The data profiles areselected in the hardware configuration program/PLC configuration program.The following three data profiles are available for the PKE-SWD-32:Table 15: Data profile for PKE-SWD-324.9.3.1 Special considerations when using the module with a CANopen field busWhen using data profile 1, 3 in conjunction with SmartWire gateway EU5C-SWD-CAN, entries in the setting range for associated service data objects(SDO) 2102subx must be changed in the PLC configuration program. Withprogramming system CoDeSys, for example, change the default value from0x2093 to 0x2094 to use PKE profile 3.In programming systems with a controller configurator without automaticprofile selection for SDO parameterization the corresponding SDO object2102subx is inserted in the SDO object list and its content transferred whendata profile 1 or 3 is used.Data profile Input byte 4 Input byte 3 Input byte 2 Input byte 1 Input byte 0PKE-SWD-32Profile 1(Moeller)– – – ✓ ✓PKE-SWD-32Profile 2(Moeller)– ✓ ✓ ✓ ✓PKE-SWD-32Profile 3(Moeller)✓ ✓ ✓ ✓ ✓Object 2102subx (x represents theposition of the PKE-SWD-32 modulein the SmartWire-DT line)contentsProfile 1 0x2091)Profile 2 (default) 0x2093)Profile 3 0x2094)→ Data bytes that are not transferred cyclically in certain profilescan still be read as acyclical data objects (→ Section4.9.4, „Acyclic data“, page 119).