10 Interface module MCB-HK-SWD for circuit-breakers and residual current circuit-breakers10.5 CommissioningSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 217▶ Use the SmartWire-DT socket to connect the 8-conductor SmartWire-DTcable to the top or bottom of the device.Due to EMC reasons, the SmartWire-DT socket strip that remainsunused must be covered with included accessory SWD4-…. Failure to doso may result in communication problems and in SWD modules beingdamaged and ruined.Figure 89: Connecting the SmartWire-DT cable10.5 CommissioningWhile addresses are being assigned, the SWD modules' SmartWire-DT diag-nostic LED will flash. Once the addresses have been successfully assigned,the LED will show a continuous green light.10.6 Exchange of modulesWhenever you replace a module, you will need to press the configurationbutton after replacing the module and switching on the voltage. When this isdone, the new module will be assigned an address.10.7 Device statusThe individual SWD modules indicate their device status with the aid of adiagnosis LED.→ For detailed instructions for adapting the SmartWire-DT externaldevice plug (SWD4-8SF2-5) to the 8-pole SmartWire-DT cable,see chapter "Fitting external device plug SWD4-8SF2-5“ of man-ual “SmartWire-DT, the System” (MN05006002Z-EN, previ-ously AWB2723-1617en).