2 I/O modules EU5E-SWD…2.12 Analog module EU5E-SWD-4AX48 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com2.12.4 InstallationFigure 21: Connecting inputs and power supply▶ Connect the analog sensors to the corresponding inputs I0 to I3.▶ Connect the 24 V power supply for the card.2.12.5 Parameter definitionWith the programming system’s control configurator, users can define thesensor model, measured value refresh rate and averaging.This setting applies for all channels.The specified value is the refresh time to the SmartWire-DT coordinator. Anaveraging function, which smooths input signal fluctuations, is associatedwith this setting.U/I0 V24 V DC+U/I+U/I+U/I+24 V0 VI0–I2+I1–I1+I0+I2–I3+I3–Parameter Setting options Default settingSensor type I0 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)Sensor type I1 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)Sensor type I2 Voltage (0 - -10 V), current (0 - 20 mA) Voltage (0 - 10 V)Sensor type I3 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)Parameter Reading refresh rate AveragingOn (default) offReading refresh rate 20 ms 1 –100 ms (default setting) 5 measurement cycles200 ms 10 measurement cycles500 ms 25 measurement cycles