4 PKE-SWD-32, interface for motor-starter combination with PKE12/324.1 IntroductionSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 834 PKE-SWD-32, interface for motor-starter combination with PKE12/324.1 IntroductionThe PKE-SWD-32 SmartWire-DT module is used to enable a PLC to control amotor-starter combination based on the PKE motor protective circuit breaker,and to receive the signals of the contactor and those of the PKE motor pro-tective circuit breaker. The PKE-SWD-32 is snap fitted directly to a DILM7 toDILM32 contactor and connected to the trip block of the PKE via a datacable.The interoperability requirements for these SWD modules are described in→ Section 14.5, „SWD module interoperability requirements“, page 258.→ Operation and installation of electronic motor-protective circuit-breaker PKE are described in document MN03402004Z-DE (for-mer designation AWB1210-1631).NOTICEThe communication connection of the PKE 12/32 is only possi-ble when using PKE trip blocks of part no. “Advanced”, i.e. PKE-XTUA-….NOTICENo additional auxiliary contact block can be snapped onto thecontactor. The auxiliary switches integrated into the contactorcan be used, for example, as safety locking devices.CAUTIONIn addition to the basic devices (contactors, motor starter combi-nations, etc.) described in the individual sections, The Smart-Wire Device Technology (SmartWire-DT) function elementslisted in this manual can also be combined with equivalentEaton basic devices that use the Eaton catalog number as partnumber. For a reference table, see the Appendix on Page 259.