11 M22-SWD-NOP and M22-SWD-NOP-C SmartWire-DT universal modules11.3 ProjectionSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 221Figure 91: M22-SWD-NOPC in enclosure M22-I311.3 ProjectionIn the PLC’s control configuration, program the SWD modules that will berequired at a later date in addition to the ones that will be installed and usedimmediately. For modules that are to be replaced with a universal module,parameter “Replacement by universal module” must be set to “allowed” inthe Module Properties dialog In the control configuration. You can then fit auniversal module in place of this SWD module in the network.In the user program scan whether the the configured SWD module or a uni-versal module is fitted. Bit 7 (SUBST) in the first input byte is set if a universalmodule is fitted in place of the software-configured module. The programflow must be controlled according to this information.The input data from a universal module always has a zero value. If a universalmodule is later replaced with the originally configured SWD module, add thismodule to the SmartWire-DT network by pressing the “Config.” button onthe gateway.M22-(C)K(C)...M22-(C)K(C)...M22-SWD-KC11M22-SWD-LEDCM22-SWD-SEL-8-10M22-SWD-NOPC2 3 12 3 1132132132INOUTOFFONINOUTPUSH!PUSH!