11 M22-SWD-NOP and M22-SWD-NOP-C SmartWire-DT universal modules11.5 CommissioningSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 22311.4.2 Base fixingUniversal module M22-SWD-NOPC is fitted to card M22-SWD-I...-LP… insurface mounting enclosure M22-I….To do so, proceed as follows:▶ Insert the printed circuit board into the surface mounting enclosure.Ensure that the PCB is pointing in the correct direction. The direction ofthe arrow defines the arrangement of the modules. (the gateway is to theleft of the IN code.)▶ Equip the slots with the M22-SWD-NOPC universal module. Ensure thatthe mounting position is correct (status LED must be at the top). Equipunused slots with the link M22-SWD-SEL8-10.Figure 94: Universal module M22-SWD-NOPC in enclosure M22-I311.5 CommissioningThe automatic addressing of all modules in the SmartWire-DT network is per-formed via the gateway during commissioning. Press the configuration but-ton on the gateway.While addresses are being assigned, the SmartWire-DT diagnostic LED onthe back of the M22 SmartWire-DT universal module will flash. Once theaddressing process is completed, the LED indicates a green continuous light.11.5.1 Exchange of modules132132132INOUTOFFONON OFFM22-SWD4-SF8-20M22-SWD4-SM8-20M22-I…NOTICESwitch off the entire SmartWire-DT system before replacingSmartWire-DT universal modules.NOTICEThe order of the SmartWire-DT units must not be altered.