14 Appendix14.6 Technical Data270 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com14.6.4 DIL contactor modulesDIL-SWD-32-001 DIL-SWD-32-002GeneralStandards IEC/EN 61131-2, EN 50178,IEC/EN 60947Dimensions (W x H x D) mm 45 x 38 x 76 45 x 38 x 76Weight kg 0.04 0.04mounting on DILM7 - DILM38Mounting position as DILM7 - DILM38Ambient mechanical conditionsDegree of protection (IEC/EN 60529, EN50178, VBG 4) IP20 IP20Vibrations (IEC/EN 61131-2:2008)constant amplitude 3.5 mm Hz 5 - 8.4 5 - 8.4Constant acceleration, 1 g Hz 8.4 - 150 8.4 - 150Mechanical shock resistance (IEC/EN 60068-2-27)semi-sinusoidal 15 g/11 msImpactresis-tances9 9Drop to IEC/EN 60068-2-31 Dropheightmm 50 50Free fall, packaged (IEC/EN 60068-2-32) m 0.3 0.3Electromagnetic compatibility (EMC)Over voltage category II IIPollution degree 2 2Electrostatic discharge (IEC/EN 61131-2:2008)Air discharge (Level 3) kV 8 8Contact discharge (Level 2) kV 4 4Electromagnetic fields (IEC/EN 61131-2:2008)80 - 1000 MHz V/m 10 101.4 - 2 GHz V/m 3 32 - 2.7 GHz V/m 1 1Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class ABurst (IEC/EN 61131-2:2008, Level 3)CAN/DP bus cable kV 1 1SmartWire-DT cables kV 1 1Radiated RFI (IEC/EN 61131-2:2008, Level 3) 10 10Ambient climatic conditionsOperating ambient temperature (IEC 60068-2) °C -25 to +60 -25 to +60Condensation prevent with suitable measuresStorage °C -30 to +70 -30 to +70relative humidity, non-condensing(IEC/EN 60068-2-30)% 5 - 95 5 - 95SmartWire-DT networkModule type SWD module (slave)Baud rate setting AutomaticStatus SmartWire-DT LED green/orangeConnections Plug, 8-poleplug connector External device plug SWD4-8SF2-5Device supply voltageSWD moduleU SWD V DC, (%) 14.5 (±3)Current consumption at U SWD → Page 253Operating modeManual/automatic mode no yesSetting – Rotary switchesConnection auxiliary contact