1 EU5C-SWD-PF1-1, EU5C-SWD-PF2-1 power modules1.3 EU5C-SWD-PF2-1SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 171.3.2 Projection1.3.2.1 Area of application of the SmartWire-DT power module EU5C-SWD-PF2-1• The supply for the modules installed in the SmartWire-DT network is nolonger sufficient (power consumption > 0.7 A).• The supply for the contactors installed in the SmartWire-DT network is nolonger sufficient (power consumption of the contactors > 72 W / 3 A).• A selective emergency shutdown of individual contactor groups or motorstarter groups is required (→ Chapter 3, “Switching onDIL-SWD-32-001, DIL-SWD-32-002 contactors”, Page 63)1.3.3 InstallationThe SmartWire-DT power module EU5C-SWD-PF2 is envisaged for mountingon a top-hat rail.▶ Mount the module on the top hat rail.▶ Connect the 24 V DC voltage to the terminals POW on the front of themodule.▶ If necessary, reconnect the 24 V DC voltage for the contactor coils to theterminals AUX.▶ Connect the 8 pole SmartWire-DT cable to the SWD In socket. The con-tinuation to the next SmartWire-DT module is from the SWD Out socket.The connection terminals are suitable for cables AWG24 to AWG16 and flex-ible conductors with a cross section of 0.5 to 1.5 mm2.Figure 4: Terminal capacity• flexible, cross-section 0.25 mm² to 1.5 mm², with the ferrule (minimumlength 8 mm)→ With a SmartWire-DT power module a second incoming unit forthe contactor coil control voltage can be made at another posi-tion in the SmartWire-DT network.24V0VPOWAUX24V0VAUX24V0V24 V DC0 VF1 F2 F2