2 I/O modules EU5E-SWD…2.9 Digital module EU5E-SWD-4D4D-R34 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com2.9 Digital module EU5E-SWD-4D4D-R2.9.1 IntroductionThe EU5E-SWD-4D4D-R SmartWire-DT I/O module features four digitalinputs (I0 to I3) and four digital outputs (Q0 to Q3).The inputs can be used to integrate various sensors into the SmartWire-DTnetwork.The short-circuit proof outputs are used to drive actuators.The module is retentive, i.e., the outputs' state will be maintained even ifthere is a power failure, loss of communication, or PLC stop.The inputs'/outputs' status is indicated with the help of LEDs.Finally, the SmartWire-DT diagnostic LED is used to signal the network's/module's status.2.9.2 Surface mountingFigure 14: Connections of the modules EU5E-SWD-4D4D-R2.9.3 EngineeringThe maximum current draw for each output is 0.5 A. The outputs are short-circuit proof. In the event of a short-circuit, the SmartWire-DT diagnostic LEDwill flash and the diagnostic bit will be set in the user program. Once theshort-circuit is removed, the outputs will be ready for operation again.By configuring the module accordingly, the outputs' behavior can be changedso that the output state will not be reset automatically in certain scenarios,e.g., a communication error on the field bus or a PLC stop.abcdfea SmartWire-DT cable with external device plugb SmartWire-DT diagnostics LEDc Status LEDs of the inputs and outputsd I0 – I3 (inputs)e Q0 - Q3 (outputs)f 0-V-24-V connection