6 PKE-SWD-CP Connection for circuit-breaker PKE6.6 Exchange of modules142 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com6.6 Exchange of modulesAfter replacing the modules and turning on the voltage, you will have topress the configuration button. When this is done, the new module will beassigned an address.6.7 Device statusThe individual SWD modules indicate their device status with the aid of adiagnosis LED. The diagnostics LED can have the following states:Table 24: Diagnostic messages of the SmartWire-DT status LED6.8 Parameter definitionDepending on the coordinator being used, the module's parameters willneed to be configured in the programming system or in the SWD-Assist plan-ning and commissioning program.6.9 Fieldbus-specific characteristicsField bus EthercatPlease note the general information for configuring parameters→ Chapter 13 “Using SWD modules with the EtherCAT field bus”, page247.NOTICEThe order of the SmartWire-DT units must not be altered. DANGERThe SWD module must not be swappedunless the entire SmartWire-DT system has been switched offfirst.designation Color Status MessageReady Green Continuous light Device is operating error-free.Flashing (1 Hz) • Addressing process in progress• After the coordinator is powered on• after actuation of the configuration button on the coordinator• Module not in current configuration• invalid typeFlashing (3 Hz) • Communication to trip block PKE is interrupted• The trip block is not of part no. PKE-XTU(W)ACP-...