14 Appendix14.6 Technical Data276 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com14.6.7 M22-SWD connectionsM22-SWD-K11/M22-SWD-KC11M22-SWD-LED-…/M22-SWD-LEDC-…M22-SWD-K11LED-…/M22-SWD-K11LEDC-…M22-SWD-K11/M22-SWD-KC11M22-SWD-LED-…/M22-SWD-LEDC-…M22-SWD-K11LED-…/M22-SWD-K11LEDC-…M22-SWD-RM22-SWD-INCGeneralStandards IEC/EN 61131-2, EN 50178Dimensions (W x H x D) mm 12 x 42 x 39/12 x 45 x 3710 x 42 x 45/10 x 45 x 4212 x 42 x 45/12 x 45 x 4212 x 42 x 45/12 x 45 x 42Weight g 10 10 10 10Mounting position AnyAmbient mechanical conditionsDegree of protection (IEC/EN 60529,EN50178, VBG 4)IP20 IP20 IP20 IP20Vibrations(IEC/EN 61131-2:2008)constant amplitude 3.5 mm Hz 5 5 - 8.4 5 - 8.4 5 - 8.4constant acceleration 1 g Hz 8.4 - 150 8.4 - 150 8.4 - 150 8.4 - 150Mechanical shock resistance(IEC/EN 60068-2-27)semi-sinusoidal 15 g/11 msImpactresis-tances9 9 9 9Drop(IEC/EN 60068-2-31);drop heightmm 50 50 50 50Free fall, packaged(IEC/EN 60068-2-32)m 0.3 0.3 0.3 0.3Electromagnetic compatibility (EMC)Over voltage category Not applicablePollution degree 2 2 2 2Electrostatic discharge (IEC/EN 61131-2:2008)Air discharge (Level 3) kV 8 8 8 8Contact discharge (Level 2) kV 4 4 4 4Electromagnetic fields (IEC/EN 61131-2:2008)80-1000 MHz V/m 10 10 10 101.4 - 2 GHz V/m 3 3 3 32 - 2.7 GHz V/m 1 1 1 1Radio interference suppression (Smart-Wire-DT)EN 55011 Class ABurst (IEC/EN 61131-2:2008, Level 3)Supply cables kV 2 2 2 2SmartWire-DT cables kV 1 1 1 1Radiated RFI (IEC/EN 61131-2:2008, Level 3)V 10 10 10 10Ambient climatic conditionsOperating ambient tempera-ture (IEC 60068-2)?C –30 - +55 –30 - +55 –30 - +55 –30 - +55Condensation prevent with suitable measuresStorage °C –40 - 80 –40 - 80 –40 - 80 –40 - 80Relative humidity, non-condensing (IEC/EN 60068-2-30)% 9 - 95 9 - 95 9 - 95 9 - 95SmartWire-DT networkModule type SWD module (slave)Baud rate setting Automatic Automatic Automatic Automatic