5 Connection PKE-SWD for motor-protective circuit-breaker PKE12/32/655.2 Surface mounting122 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com5.2 Surface mountingFigure 55: Figure 1: Connections PKE-SWDa Connection of SmartWire-DT external device plugb Diagnostics LEDc Engagement hook for connecting to PKE basic deviced Data interface for PKE control option “Advanced”The SmartWire-DT external device plug with an adapted SmartWire-DT con-necting cable is connected to the module PKE-SWD via connection 1.Diagnostic LED ② indicates the module’s communication status through theSmartWire-DT system and the communication state to the PKE trip block(→ Section 5.7, „Device status“, page 126).The PKE-SWD is fixed to the corresponding basic devices PKE with theengagement hook ③. This must be operated before the PKE-SWD isremoved. When installing the PKE-SWD, the PKE basic device must not befitted with a PKE trip block.PKE-SWD and PKE trip block communicate through the data interface ④.5.3 EngineeringThe PKE-SWD can be combined with motor-protective circuit-breakersPKE12, PKE32 and PKE65. The trip blocks used that can be combined withthe PKE basic devices must be of type XTUA or PKE-XTUWA. For each PKE-SWD one motor-protective circuit-breaker PKE with PKE trip block can beconnected.The following trip blocks of the type “Advanced” can be combined with thetwo PKE basic devices PKE12, PKE32 and PKE65.→ For detailed instructions on how to connect the SmartWire-DTexternal device plug (SWD4-8SF2-5) to the 8-pin SmartWire-DTribbon cable, refer to the "Installing SWD4-8SF2-5 externaldevice plugs" section in manual MN05006002Z-EN (previouslyAWB2723-1617de).①②③④