4 PKE-SWD-32, interface for motor-starter combination with PKE12/324.3 ProjectionSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 87Figure 40: Connections PKE-SWD-32 and PKE32-COM-Modulea Connection of SmartWire-DT external device plugb Mechanical switching position indicatorc Diagnostics LEDd Catch slidere Connection pinsf Adjusting slide for contactor sizeg Data interface for PKE32-COMh Connection terminal, electrical enable X3-X4i Selector switch 1-0-Aj Data cable with connector for PKE-SWD-32k Connector for PKE-XTUA- trip block...4.3.1 DOL startersThe DOL starters are assembled from a PKE12/ PKE32 with the PKE-XTUA-… trip block and a DILM7 to DILM32 contactor.The PKE-SWD-32 is fitted onto the contactor.The PKE32-COM is used as a communication link between the PKE-SWD-32and the PKE trip block. The PKE-SWD-32 receives the data of the PKE tripblock via the PKE32-COM and makes this available as input data on theSmartWire-DT network.The PKE32-COM is mounted to the PKE basic device (PKE12 or PKE32). Theconnector located above the PKE32-COM ⑪ makes the contact with thedata interface of the PKE trip block. The data cable with the connector forthe PKE-SWD-32 ⑩ is connected via the data interface ⑦ to the PKE-SWD-32.①②③ ④ ⑤⑥⑦⑧⑨⑩⑪PKE-SWD-32 PKE32-COMNOTICEThe PKE-SWD32 controls the contactor so the terminals A1-A2must not be wired.