7 Electronic motor starter EMS-…-SWD-ADP7.8 Programming168 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com7.8.3 Cyclical output dataByte 0:Control section operating direction7 6 5 4 3 2 1 0– – – – RES_AUT RES_MAN CMD_DIRL CMD_ON/CMD_DIRRdata bit designation Description0 CMD_ON/CMD_DIRR0: No actuation signal for motor start(EMS-DO-… DOL starter) orclockwise operation motor start (EMS-RO-… reversing starter)1: Motor start or clockwise operation motor start1 CMD_DIRL 0: No actuation signal for anticlockwise operation motor start1: Motor start anticlockwise operation2 RES_MAN 0: No control section signal for manual overload case reset1: Overload case activated by rising edge 1)3 RES_AUT 0: No activation signal for automatic overload case reset1: Overload case activated by permanent signal2)1) The electronic motor starter will be ready to receive a manual reset (RES_MAN) command 2 minutesafter an overload trip.2) For automatic resetting, the automatic resetting command (RES_AUT) must already be set before theoverload trip. The motor will be restarted automatically (with the activated operating direction) after 20minutes.