2 I/O modules EU5E-SWD…2.9 Digital module EU5E-SWD-4D4D-RSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 37Fieldbus EtherCATPlease refer to the general information on how to configure the relevantparameters → Chapter 13 “Using SWD modules with the EtherCAT fieldbus”, page 247, especially→ Section , „Device options“, page 247.device index: sub-index 22Parameter data length: 0x02Structure of parameter byte 1: Retention behavior2.9.7 ProgrammingThe module has two input bytes and one output byte at its disposal.2.9.7.1 InputsByte 0: Status SmartWire-DTBit Parameter Configuration Default0 Retention behaviorOutput Q01: Output Q0 will retain its state even if commu-nication drops out or the PLC stops0: Output Q0 will reset0: Output Q0 will reset1 Retention behaviorOutput Q11: Output Q1 will retain its state even if commu-nication drops out or the PLC stops0: Output Q1 will reset0: Output Q1 will reset2 Retention behaviorOutput Q21: Output Q2 will retain its state even if commu-nication drops out or the PLC stops0: Output Q2 will reset0: Output Q2 will reset3 Retention behaviorOutput Q31: Output Q3 will retain its state even if commu-nication drops out or the PLC stops0: Output Q3 will reset0: Output Q3 will reset4-7 reserved 0 0Bit Parameter Configuration Default0 Retention behaviorOutput Q01: Output Q0 will retain its state even if commu-nication drops out or the PLC stops0: Output Q0 will reset0: Output Q0 will reset1 Retention behaviorOutput Q11: Output Q1 will retain its state even if commu-nication drops out or the PLC stops0: Output Q1 will reset0: Output Q1 will reset2 Retention behaviorOutput Q21: Output Q2 will retain its state even if commu-nication drops out or the PLC stops0: Output Q2 will reset0: Output Q2 will reset3 Retention behaviorOutput Q31: Output Q3 will retain its state even if commu-nication drops out or the PLC stops0: Output Q3 will reset0: Output Q3 will reset4-7 reserved 0 07 6 5 4 3 2 1 0SUBST PRSNT – DIAG – – – –