3 Switching on DIL-SWD-32-001, DIL-SWD-32-002 contactors3.5 CommissioningSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 793.5 CommissioningThe automatic addressing of all modules in the SmartWire-DT network is per-formed via the gateway (actuation of the configuration pushbutton on thegateway) during commissioning. During the addressing process the Smart-Wire-DT diagnostics LED flashes. Once the addressing process is com-pleted, the LED indicates a green continuous light.3.6 Exchange of modulesAfter replacement of the modules and connection of the voltage the configu-ration button must be pressed. When this is done, the new module will beassigned an address.3.6.0.1 Motor starter or contactor3.7 Device statusThe individual SmartWire-DT modules indicate their device status with theaid of a diagnosis LED.Table 6: Diagnostic alarms of the SmartWire-DT module for DILM (LED indicator) DANGERThe exchange of the SmartWire-DT module for DILM must onlybe carried out with the supply switched off.NOTICEThe order of the SWD modules must not be altered. DANGERThe exchange of the motor starter or contactor must only becarried out after the complete system SmartWire-DT isswitched off.designation Color Status MessageReady Orange Continuous light Switching command for contactor viaSmartWire-DTGreen Continuous light Device is operating fault-free.flashing (1 Hz) • addressing process in progress• after gateway power On• after actuation of the configurationbutton on the gateway• Module not in current configuration• invalid type