3 Switching on DIL-SWD-32-001, DIL-SWD-32-002 contactors3.3 EngineeringSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 653.3 EngineeringSmartWire-DT modules DIL-SWD-32-001 and DIL-SWD-32-002 can be com-bined with circuit breakers DILM7 to DILM38. This allows the use of motorstarters consisting of a motor-protective circuit-breaker PKZ and a contactorDILM with the SmartWire-DT system.With contactor combinations a SmartWire-DT module for DILM is requiredfor each contactor.Table 3: Combination optionsAs well as with contactors the SmartWire-DT module for DILM can also becombined with all DILA contactor relays.The contactor´s power supply is directly supplied via the SmartWire-DT con-nection cable. The contactor coils have the following power consumptionswith a voltage of 24 V DC:Table 4: Power consumptions of the contactor coils with a voltage of 24 V DCUse Number of SmartWire-DT modules for DILMDILM contactor 1Motor starter MSCDOL starter (PKZ and DILM) 1Reversing starters 2Reversing combination 2→ Contactors with a rated operational current greater than 38 Acan be integrated into the SmartWire-DT system with a DILA asa coupling relay or SmartWire-DT I/O module.contactor Pull-in power Pick-up currentwith 24 V DCSealing power Holding currentwith 24 V DC[W] [mA] [W] [mA]DILA, DILM7 3 125 3 125DILM9 – DILM15 4.5 188 4.5 188DILM17 – DILM38 12 500 0.5 21NOTICEThe sum of the pull-in power of the simultaneously tripping con-tactors and the sum of the holding power of the tripped contac-tors for each SmartWire-DT network must not exceed 72 W. Ifrequired, an additional power feeder module (EU5C-SWD-PF1-1,EU5C-SWD-PF-2) must be used(→ Chapter 1 “EU5C-SWD-PF1-1, EU5C-SWD-PF2-1 powermodules”, page 13)