9 SL4-SWD and SL7-SWD base modules for signal towers9.5 Commissioning212 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com9.5 CommissioningOnce all the SWD modules are connected to the SWD line, you will need theSmartWire-DT coordinator to automatically assign addresses to all of them.To do this, press the configuration button on the front of the SmartWire-DTcoordinator.During the address assignment process, the SWD modules' module LED willflash. If the process is completed successfully, the module LED will show acontinous green light.9.5.1 Exchange of modulesAfter replacing the modules and turning on the voltage, you will have topress the configuration button. When this is done, the new module will beassigned an address.9.5.2 Device statusThe individual SWD modules indicate their device status with the help of amodule LED.Table 49: Module LED diagnostic messages9.6 Parameter definitionDepending on the coordinator being used, the module's parameters willneed to be configured in the programming system or in the SWD-Assist plan-ning and commissioning program.NOTICESwitch off the entire SmartWire-DT system before replacingSmartWire-DT base modules.NOTICEThe order of the SmartWire-DT units must not be altered.designation Color Status MessageModule-LED Green Continuous light Device is operating fault-free.flashing (1 Hz) • addressing process in progress• after gateway power On• after actuation of the configuration button on thegateway• Module not in current configuration• invalid typeoff no 15 V supply voltage