3 Switching on DIL-SWD-32-001, DIL-SWD-32-002 contactors3.4 InstallationSmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com 773.3.7.3 Reversing starterBesides the special features described in the aforegoing subsection “Directstarters”, it must be taken into account that reversing starters in the NorthAmerican market must be equipped in addition with a mechanical and electri-cal locking device. The electrical locking is realized via the connection auxil-iary contact "Enable" → Figure 30, ⑧.3.4 InstallationThe SmartWire-DT modules DIL-SWD-32-001 and DIL-SWD-32-002 for DILMmust be adapted to the corresponding contactor size prior to mounting. Theadjustment required for this is performed by means of the adjusting slide ofthe SmartWire-DT module for DILM.▶ Set the setting slider on the SmartWire-DT module for the correspondingcontactor:• Bottom position: DILA, DILM7, DILM9, DILM12, DILM15• Top position: DILM17, DILM25, DILM32, DILM38NOTICEThe SmartWire-DT module for DILM may be installed anddetached only after the control voltage and supply cable havebeen switched off.Position bottom Position topFigure 35: Adjustment of the adjusting slide on DIL-SWD-32-001 or DIL-SWD-32-002