2 I/O modules EU5E-SWD…2.14 Analog modules EU5E-SWD-4PT and EU5E-SWD-4PT-258 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com2.14.4 installationFigure 25: Connecting inputs and supply of module EU5E-SWD-4PT/...4PT-2▶ Connect the sensors to the corresponding inputs I0 to I3.▶ Connect the 24 V power supply for the card.2.14.5 Parameter settingWith the programming system’s control configurator, users can define thesensor model, measured value refresh rate and analog input representation.This setting applies for all analog inputs. The specified value is the refreshtime to the SmartWire-DT network. An averaging function, which smoothsinput signal fluctuations, is associated with this setting.0 V24 V DCRTDRTD24 V0 VRTDB0a0A0B1a1A1B2a2A2B3a3A3parameter Setting options Basic SettingSensor type 1 Not used, PT100, PT1000, Ni1000 Not UsedSensor type 2 Not used, PT100, PT1000, Ni1000 Not UsedSensor type 3 Not used, PT100, PT1000, Ni1000 Not UsedSensor type 4 Not used, PT100, PT1000, Ni1000 Not UsedApplication Style Degrees Celsius, degrees Fahrenheit, nonlinearvalueDegrees Celsiusparameter Reading refresh rate AveragingReading refresh rate/aver-aging0.25 s (default setting) –1 s 4 measurement cycles2.5 s 10 measurement cycles10 s 40 measurement cycles