14 Appendix14.6 Technical Data274 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com14.6.6 Electronic motor starter EMS-…-SWD-ADPEMS-...-2.4-SWD-ADPEMS-...-9-SWD-ADPGeneralStandards IEC/EN 60947-4-2Dimensions (W x H x D) mm 30 x 157 x 139Weight kg 0.32mounting on mounting railMounting position horizontal / verticalDegree of protection (IEC/EN 60529, EN50178, VBG 4) IP20Ambient climatic conditionsOperating ambient temperature (IEC 60068-2) °C -25 to +60Condensation prevent with suitable measuresStorage °C -40 to +80Dielectric strengthOver voltage category IIPollution degree 2Measurement of the clearance and creepage distance EN 50178, UL 508, CSA C22.2, No. 142Dielectric strength EN 50178Rated surge voltage invariability kV 6Electromagnetic compatibility (EMC)Electrostatic discharge (DIN EN 61000-4-2)Air discharge (Level 3) kV 8Contact discharge (Level 2) kV 6Electromagnetic fields (DIN EN 61000-4-3)80 - 1000 MHz V/m 101.4 - 2 GHz V/m 32 - 2.7 GHz V/m 1Radio interference suppression (DIN EN 61000-6-4) Class ABurst (DIN EN 61000-4-4)Main circuits kV 2SmartWire-DT cables kV 1Fieldbus cable kV 1Surgesymmetric kV 0.5asymmetric kV 1EMC-inflow (DIN EN 61000-4-6) V 10SmartWire-DT interfaceModule type SWD module (slave)Baud rate setting AutomaticStatus SmartWire-DT LED greenConnection Pin contact, 8 pole;Plug connector: blade terminal SWD4-8MF2Device supply voltageSWD moduleU SWD V DC, (%) 14.5 (±3)Current consumption at U SWD → Page 253Potential separationto supply voltage UAUX yesSupply voltage AUXRated operational voltage U e VDC,(%)24 (-15/+20)Residual ripple % –Max. power consumption at U AUX A 60Notes 1) Minimum length 8 mm