3 Switching on DIL-SWD-32-001, DIL-SWD-32-002 contactors3.8 Programming80 SmartWire-DT modules IP20 09/17 MN05006001Z EN www.eaton.com3.7.1 Parameter definitionDepending on the coordinator being used, the module's parameters willneed to be configured in the programming system or in the SWD-Assist plan-ning and commissioning program.3.7.2 Fieldbus-specific characteristicsField bus EthercatPlease note the general information for configuring parameters→ Chapter 13 “Using SWD modules with the EtherCAT field bus”, page247.3.8 Programming3.8.1 DIL-SWD-32-001The function element has one input byte and one output byte at its disposal.3.8.1.1 InputsByte 0:7 6 5 4 3 2 1 0SUBST PRSNT – DIAG – I1 (X1-X0)I0 (X1-X2)CcBit designation Meaning0 C = Contactor 0: contactor not tripped1: contactor tripped1 I0 (X1-X2) 0: Auxiliary contact for X1-X2 opened1: Auxiliary contact for X1-X2 closedThe meaning depends on the auxiliary switch used.2 I1 (X1-X0) 0: Auxiliary contact for X1-X0 opened1: Auxiliary contact for X1-X0 closedThe meaning depends on the auxiliary switch used.3 Not used –4 DIAG 0: no diagnostic alarm5 Not used –6 PRSNT 0: Module not available1: Module available7 SUBST 0: Configured module present1: Universal module M22-SWD-NOP(C) present