i-on Range Installer Menu OptionsPage 93Notes:1. If a user causes an alarm which would require Installer reset then they have a timeto abort the alarm, which they can then reset themselves. The time allowed foraborting the alarm can be set by the Abort Timer, see page 100.2. These options apply to intruder alarms only and not to HUAs. However, if aconfirmed HUA is started by an initial Tamper alarm, and tamper reset is set to“Installer”, then the installer will have to reset the system after that HUA.HUA Confirm TimeThis option determines the length of the confirmation time for confirmed HUAs. You cankey in any time between a minimum of eight hours and a maximum of 20 hours.Note that the time must be between eight hours and 20 hours in order to comply withBS8243:2010 5.4.1.2.If the confirmation time expires after an unconfirmed HUA, and the HUD is still active, thenthe control unit omits the active device and communicates “Omitted HUD” to the ARC. Ifthe system is unset the control unit displays an alert at the appropriate keypads.If you wish to generate a confirmed HUA for test purposes only then you can set the HUAconfirm time to “0”. Please note that this setting does not comply with BS8243:20105.4.1.2.Tamper as Tamper OnlyThe purpose of the option is to ensure strict compliance with BS8243 when reportingTampers to ARCs. There are two options:Enabled When an unconfirmed Tamper occurs the control unit sends only “Tamper”to the ARC and activates any output programmed as “Tamper” (thisfollows Eaton’s Security Business’s understanding that BS8243, AnnexH.7.1 applies to all Grades).Disabled When an unconfirmed Tamper occurs the control unit sends “Tamper”,“General Fault” and “Burg” to the ARC. In addition it activates any outputsprogrammed as “Tamper” and “General Fault”. (See also Jamming onpage 101 and Supervision on page 100.)Note: This option does not comply with BS8243.This option appears only if Confirmation Mode is set to “BS8243”, and is initially set to“Enabled”. The option is set to “Disabled” and hidden when the Confirmation Mode is setto “Basic” or “DD243”.Note: If using Fast Format communications please ensure that one channel is allocated forTamper. If you do not do this then the control unit reports tamper as an unconfirmedBurg to ensure the condition is notified.Profiles16 40In the i-on16 and i-on40 control units this option loads a set of standard entries for allnames, and sets up other options. Once you have loaded the profile you can edit any ofthe settings to suit an individual installation.