i-on Range The Installer MenuPage 37MENU Option Factory Default NotesOn time 1 second Appears when Pulsed set to “Yes”.3 SETTING OPTIONS Appears only in a Part Settingsystem.Full SetName “Full Set”Exit mode Timed SetSettle time 15 seconds Appears only if Exit Mode is “FinalDoor”, “Lock Set” or “ExitTerminate”.Exit time 40 seconds Appears only if Exit Mode is“Timed Set” or “Silent Set”.Entry time 40 seconds To comply with EN50131-1 Clause8.3.8.2, maximum is 45sSiren Delay 0 minutesSiren Time 15 minutes To comply with EN50131-1 Clause8.6 minimum is 90s, maximum is15mins.Strobe on Set OffStrobe on Unset OffPart Set BName “Part Set B”Exit Mode Instant SetSettle time 15 seconds Appears only if Exit Mode is “FinalDoor”, “Lock Set” or “ExitTerminate”.Exit time 40 seconds Appears only if Exit Mode is“Timed Set” or “Silent Set”.Entry time 40 seconds The maximum time permitted byEN50131-1 Clause 8.3 is 45seconds.Alarm Response Siren Includes Internal AlarmSiren Delay 0 minutesSiren Time 15 minutes To comply with EN50131-1 Clause8.6 minimum is 90s, maximum is15mins.Part Set Final Exit Final exitPart Set Entry Route Entry RouteStrobe on Set Off This setting is required in order tocomply with EN50131.Strobe on Unset OffPart C, D (See Part Set B)Calendar Set None 50 1603. PARTITION Appears only in a Partitionedsystem (not on i-on16)Partition 1Name “Partition 1”Exit Mode Timed Set All partitions higher than 1 defaultto the same exit mode as partition1.Settle Time 15 seconds Appears only if Exit Mode is “FinalDoor”, “Lock Set” or “ExitTerminate”.Exit Time 40 seconds Appears only if Exit Mode is“Timed Set” or “Silent Set”.Entry Time 40 seconds The maximum time permitted byEN50131-1 Clause 8.3 is 45seconds.Alarm Response Siren + CommsHUA Response Audible Appears here for partitioned