ABB Relion REG670 manuals
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- About the operator's manual
- Intended audience
- Revision notes
- Section 2 Safety information
- Section 3 Overview
- Section 4 Understand the IED local human-machine interface
- Keypad
- Key activated screens
- The Reset screen
- Introduction
- Local HMI setup
- Control
- Section 5 Understand the HMI tree
- Section 6 Read measured values
- View analog primary values
- View analog mean values
- Voltage phasors VMMXU/VNMMXU
- Function for energy calculation and demand handling ETPMMTR
- View events
- Identify a disturbance
- View trip values
- System time and synchronization
- TIMESYNCHBIN
- General settings
- SPA, LON and IEC 60870–5–103 settings
- Station communication
- Ethernet configuration
- Analog and I/O modules
- I/O modules
- Functions
- Control commands
- Synchrocheck and energizing check SESRSYN
- Current phasors CMMXU
- Disturbance report DRPRDRE
- Logical signal status report BINSTATREP
- Setting group N
- High impedance differential protection HZPDIF
- Distance protection zones, quadrilateral characteristics for series compensated lines ZMCPDIS, ZMCAPDIS
- Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS
- Additional distance protection directional function for earth faults ZDARDIR
- Breaker failure protection CCRBRF
- Instantaneous residual overcurrent protection EFPIOC
- Sensitive directional residual over current and power protection SDEPSDE
- Overexcitation protection OEXPVPH
- Overfrequency protection SAPTOF
- Scheme communication
- Fuse failure supervision SDDRFUF
- Automatic voltage control for tapchanger, parallel control TR8ATCC
- LogicGate
- Read internal events
- Overview
- IED test mode
- Signal matrix for binary input SMBI
- Impedance protection
- Transformer differential protection, three winding T3WPDIF
- Distance protection zone, quadrilateral characteristic ZMCPDIS, ZMCAPDIS
- Faulty phase identification with load enchroachment FMPSPDIS
- Directional impedance quadrilateral, including series compensation ZDSRDIR
- Current protection
- Two step overvoltage protection OV2PTOV
- Rate-of-change frequency protection SAPFRC
- Scheme communication logic for residual overcurrent protection ECPSCH
- Commands
- IEC61850 generic communication I/O functions DPGGIO
- Automatic voltage control for tapchanger, single and parallel control TR1ATCC/TR8ATCC
- Generic measured value MVGGIO
- Logic
- Logic SR/RS memory
- Setting groups
- Line differential test
- Control screen messages
- Section 13 Reset
- Reset lockout SMPPTRC
- Section 14 Authorization
- LogOn or logOff
- Internet Protocol ports security guideline
- Section 15 Glossary
Relion REG670
Table of contents
- Table Of Contents
- Application
- Available functions
- Differential protection
- Impedance protection
- Wide area measurement system
- Voltage protection
- Frequency protection
- General calculation
- Control
- Logic
- Monitoring
- Metering
- Human machine interface
- Station communication
- Remote communication
- Hardware description
- Connection diagrams
- Technical data
- Ordering for customized IED
- Ordering for pre-configured IED
- Ordering for Accessories
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Related documents
- Document symbols and conventions
- Section 2 Safety information
- Caution signs
- Note signs
- Section 3 Environmental aspects
- Section 4 Unpacking, inspecting and storing
- Returning an IED damaged in transit
- Section 5 Mounting
- Flush mounting
- Mounting procedure for flush mounting
- panel rack mounting
- Mounting procedure for 19" panel rack mounting
- Wall mounting
- Mounting procedure for wall mounting
- Side-by-side 19" rack mounting
- Mounting procedure for side-by-side rack mounting
- Side-by-side flush mounting
- Mounting procedure for side-by-side flush mounting
- Mounting the coupling capacitor unit REX061 and shunt resistor unit REX062 (REG670 only)
- Shunt resistor unit REX062
- Making the electrical connection
- Front side connectors
- Rear side connectors
- Connection examples for high impedance differential protection
- Connecting to protective earth
- Connecting the power supply module
- Connecting the binary input and output signals
- Making the shield connection
- Making the electrical connection to the rotor and stator injection equipment (REG670 only)
- Coupling capacitor unit REX061
- Connecting injection unit REX060, coupling capacitor unit REX061 and shunt resistor unit REX062
- Connecting and setting voltage inputs
- Making of Ethernet connections
- Connecting remote communication interfaces LDCM
- Installing the serial communication cable for RS485
- Installing the serial communication cable for RS485 SPA/IEC
- Data on RS485 serial communication module cable
- Electrical installation
- Section 7 Checking installation
- Section 8 Removing, repairing and exchanging
- Sending the IED for repair
- Section 9 Technical data
- Case with rear cover
- Flush mounting dimensions
- Side-by-side flush mounting dimensions
- Wall mounting dimensions
- Section 10 Glossary
Relion REG670
Table of contents
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Document symbols and conventions
- Document conventions
- Section 2 Safety information
- Caution signs
- Note signs
- Section 3 Available functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 4 Starting up
- Checking the power supply
- Energizing REX060
- Writing an application configuration to the IED
- Checking VT circuits
- Checking the binary I/O circuits
- Section 5 Configuring the IED and changing settings
- Reconfiguring the IED
- Section 6 Calibrating injection based sensitive rotor earth fault protection
- Launching injection commissioning tool (ICT) and performing the installation
- Performing calibration
- Acquiring references
- Verifying calibration
- Auditing
- Editing features in graph
- Logging measurements to file
- Section 7 Calibrating injection based 100% stator earth fault protection
- Section 8 Establishing connection and verifying the SPA/IEC communication
- Verifying the communication
- Optical budget calculation for serial communication with SPA/IEC
- Section 9 Establishing connection and verifying the LON communication
- The LON Protocol
- Optical budget calculation for serial communication with LON
- Section 10 Establishing connection and verifying the IEC 61850 communication
- Preparing for test
- Preparing the IED to verify settings
- Activating the test mode
- Connecting the test equipment to the IED
- Verifying analog primary and secondary measurement
- Forcing of binary I/O signals for testing
- Enable forcing using TESTMODE function block
- Forcing by using PCM600
- How to undo forcing changes and return the IED to normal operation
- Testing disturbance report
- Event recorder (ER) and Event list (EL)
- Verifying the settings
- Completing the test
- Measuring the operating limit of set values
- Phase-to-phase faults
- Faulty phase identification with load encroachment FMPSPDIS
- Measuring the operating time of distance protection zones
- Testing the power swing detection function ZMRPSB
- Automatic switch onto fault logic ZCVPSOF
- Activating ZCVPSOF externally
- Under impedance protection for Generator ZGVPDIS
- Testing
- Four step phase overcurrent protection 3-phase output OC4PTOC
- Four step non-directional earth fault protection
- Measuring the operate and time limit for set values
- Checking the re-trip and back-up times
- Verifying the back-up trip mode
- Verifying instantaneous back-up trip at CB faulty condition
- Checking the phase current operate value IP
- Measuring the operate limit of set values
- Accidental energizing protection for synchronous generator AEGPVOC
- Voltage protection
- Extended testing
- Check of undervoltage levels
- Check of voltage differential trip and alarm levels
- Check of trip and trip reset timers
- Final adjustment of compensation for VT ratio differences
- Verifying settings
- Rate-of-change frequency protection SAPFRC
- Overcurrent feature with current restraint
- Over/Undervoltage feature
- Measuring the operate value for the negative sequence function
- Measuring the operate value for the dead line detection function
- Testing the synchronizing function
- Testing the synchrocheck check
- Testing the energizing check
- Testing the voltage selection
- Secondary test
- Check the normal voltage regulation function
- Check the upper and lower busbar voltage limit
- Parallel voltage regulation
- ph/3ph operating mode
- Circuit breaker lockout
- Remote communication
- Exit test mode
- Overview
- Commissioning tests
- Visual inspection
- Alarm test
- Restoring
- Checking the self supervision signals
- Fault tracing
- Using front-connected PC
- Diagnosing the IED status via the LHMI hint menu
- Hardware re-configuration
- Repair instruction
- Repair support
- Section 16 Glossary
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Document symbols and conventions
- Document conventions
- Section 2 Safety information
- Caution signs
- Note signs
- Section 3 Environmental aspects
- Section 4 Unpacking, inspecting and storing
- Storing
- Section 5 Mounting
- Flush mounting
- Mounting procedure for flush mounting
- Mounting procedure for 19" panel rack mounting
- Wall mounting
- Side-by-side 19" rack mounting
- Mounting procedure for side-by-side rack mounting
- Side-by-side flush mounting
- Mounting procedure for side-by-side flush mounting
- Coupling capacitor unit REX061
- Shunt resistor unit REX062
- Section 6 Connecting
- Front side connectors
- Rear side connectors
- Connection examples for high impedance differential protection
- Connecting to protective ground
- Connecting to CT and VT circuits
- Connecting the binary input and output signals
- Making the shield connection
- Making the electrical connection to the rotor and stator injection equipment (REG670 only)
- Connecting injection unit REX060, coupling capacitor unit REX061 and shunt resistor unit REX062
- Connecting and setting voltage inputs
- Making of Ethernet connections
- Connecting remote communication interfaces LDCM
- Installing the serial communication cable for RS485
- Installing the serial communication cable for RS485 SPA/IEC
- Data on RS485 serial communication module cable
- Installing the GPS antenna
- Electrical installation
- Section 7 Checking installation
- Section 8 Removing, repairing and exchanging
- Exchanging the IED
- Section 9 Technical data
- Case with protective cover
- Flush mounting dimensions
- Side-by-side flush mounting dimensions
- Wall mounting dimensions
- Section 10 Glossary
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Related documents
- Document conventions
- IEC 61850 edition 1 / edition 2 mapping
- Section 2 Available functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 3 Analog inputs
- Signals
- Settings
- Monitored data
- Operation principle
- Section 4 Binary input and output modules
- Setting parameters for binary input/output module
- Section 5 Local Human-Machine-Interface LHMI
- Function block
- Display
- LEDs
- Keypad
- Functionality
- Indication LEDs
- Function keys
- Transformer differential protection T2WPDIF and T3WPDIF
- Function calculation principles
- Logic diagram
- Technical data
- Ph High impedance differential protection HZPDIF
- Generator differential protection GENPDIF
- Supplementary criteria
- Harmonic restrain
- Cross-block logic scheme
- Low impedance restricted earth fault protection REFPDIF
- Restricted earth-fault protection, low impedance differential protection
- Calculation of differential current and bias current
- Detection of external earth faults
- Algorithm of the restricted earth-fault protection
- Full-scheme distance measuring, Mho characteristic ZMHPDIS
- Impedance characteristic
- Basic operation characteristics
- Theory of operation
- Simplified logic diagrams
- High speed distance protection ZMFPDIS
- Distance measuring zones
- Phase-selection criteria
- Directional criteria
- Fuse failure
- Load encroachment
- Simplified logic schemes
- Phase-selection element
- Directional element
- Lens characteristic
- Detecting an out-of-step condition
- Maximum slip frequency
- Taking care of the circuit breaker
- Design
- Description of input signals
- The injection unit REX060
- Rotor Earth Fault Protection function
- General measurement of earth fault impedance
- Simplified logic diagram
- stator earth fault protection, injection based STTIPHIZ
- Generator system earthing methods
- Stator earth fault protection function
- Measuring reference impedance
- Under impedance protection for generators and transformers ZGVPDIS
- Operation principle of zone 1
- Operation principle of zone 2
- Operation principle of zone 3
- Under voltage seal-in
- Instantaneous phase overcurrent protection 3-phase output PHPIOC
- Identification
- Second harmonic blocking element
- Instantaneous residual overcurrent protection EFPIOC
- Internal polarizing
- External polarizing for earth-fault function
- Base quantities within the protection
- Directional supervision element with integrated directional comparison function
- Switch on to fault feature
- Four step directional negative phase sequence overcurrent protection NS4PTOC
- Internal polarizing facility of the function
- External polarizing for negative sequence function
- Thermal overload protection, two time constants TRPTTR
- Pole discordance signaling from circuit breaker
- Directional underpower protection GUPPDUP
- Low pass filtering
- Calibration of analog inputs
- Directional overpower protection GOPPDOP
- Start sensitivity
- Alarm function
- Voltage-restrained time overcurrent protection VRPVOC
- Generator stator overload protection, GSPTTR
- Two step undervoltage protection UV2PTUV
- Measurement principle
- Blocking
- Two step residual overvoltage protection ROV2PTOV
- Overexcitation protection OEXPVPH
- Measured voltage
- Operate time of the overexcitation protection
- Cooling
- Overexcitation alarm
- Voltage differential protection VDCPTOV
- Underfrequency protection SAPTUF
- Voltage dependent time delay
- Overfrequency protection SAPTOF
- Time delay
- Rate-of-change frequency protection SAPFRC
- General current and voltage protection CVGAPC
- Base quantities for CVGAPC function
- Built-in undercurrent protection steps
- Built-in overvoltage protection steps
- Multipurpose filter SMAIHPAC
- Filter calculation example
- Current circuit supervision CCSSPVC
- Delta current and delta voltage detection
- Dead line detection
- Main logic
- Synchrocheck, energizing check, and synchronizing SESRSYN
- Logic diagrams
- Interlocking
- Logical node for interlocking SCILO
- Interlocking for busbar earthing switch BB_ES
- Interlocking for bus-section disconnector A1A2_DC
- Interlocking for bus-coupler bay ABC_BC
- Interlocking for 1 1/2 CB BH
- Function blocks
- Interlocking for double CB bay DB
- Interlocking for line bay ABC_LINE
- Interlocking for transformer bay AB_TRAFO
- Position evaluation POS_EVAL
- Error handling
- Bay control QCBAY
- Local/Remote switch LOCREM
- Switch controller SCSWI
- Circuit breaker SXCBR
- Circuit switch SXSWI
- Bay reserve QCRSV
- Reservation input RESIN
- Voltage control
- Tap changer control and supervision, 6 binary inputs TCMYLTC and TCLYLTC
- Connection between TR1ATCC or TR8ATCC and TCMYLTCor TCLYLTC
- Logic rotating switch for function selection and LHMI presentation SLGAPC
- Graphical display
- Selector mini switch VSGAPC
- Generic communication function for Double Point indication DPGAPC
- Tripping logic common 3-phase output SMPPTRC
- Logic for group warning WRNCALH
- AND function block AND
- Set-reset with memory function block SRMEMORY
- ANDQT function block
- Reset/Set function block RSMEMORYQT
- Extension logic package
- Boolean 16 to Integer conversion B16I
- Setting parameters
- Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
- Operation accuracy
- Measurements
- Measurements CVMMXN
- Phase current measurement CMMXU
- Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU
- Gas medium supervision SSIMG
- Circuit breaker contact travel time
- Circuit breaker status
- Remaining life of circuit breaker
- Accumulated energy
- Circuit breaker operation cycles
- Circuit breaker operation monitoring
- Circuit breaker spring charge monitoring
- Circuit breaker gas pressure indication
- Event function EVENT
- Disturbance report DRPRDRE
- Logical signal status report BINSTATREP
- Measured value expander block RANGE_XP
- Reporting
- Pulse-counter logic PCFCNT
- series protocols
- LON communication protocol
- Communication ports
- IEC 60870-5-103 communication protocol
- I103MEASUSR
- Function status auto-recloser for IEC 60870-5-103 I103AR
- Function status earth-fault for IEC 60870-5-103 I103EF
- I103FLTPROT
- Supervison status for IEC 60870-5-103 I103SUPERV
- I103USRDEF
- Function commands for IEC 60870-5-103 I103CMD
- I103USRCMD
- Goose binary receive GOOSEBINRCV
- GOOSEDPRCV
- GOOSEMVRCV
- MULTICMDRCV and MULTICMDSND
- Security events on protocols SECALARM
- Binary signal transfer
- Transmission of analog data from LDCM LDCMTransmit
- Authority check ATHCHCK
- Authorization with Central Account Management enabled IED
- Authority management AUTHMAN
- Internal signals
- Supervision of analog inputs
- Time synchronization TIMESYNCHGEN
- Real-time clock (RTC) operation
- Synchronization alternatives
- ChangeLock function CHNGLCK
- Test mode functionality TESTMODE
- IED identifiers TERMINALID
- Product information PRODINF
- Signal matrix for binary inputs SMBI
- Signal matrix for mA inputs SMMI
- Frequency values
- Global base values GBASVAL
- Primary system values PRIMVAL
- Overview
- Case from the rear side
- Hardware modules
- Numeric processing module (NUM)
- Block diagram
- Introduction
- Binary input module (BIM)
- Binary output modules (BOM)
- Static binary output module (SOM)
- Binary input/output module (IOM)
- mA input module (MIM)
- Galvanic RS485 communication module
- Optical ethernet module (OEM)
- Galvanic X.21 line data communication (X.21-LDCM)
- Dimensions
- Flush mounting dimensions
- Side-by-side flush mounting dimensions
- Wall mounting dimensions
- Mounting alternatives
- Mounting procedure for flush mounting
- panel rack mounting
- Mounting procedure for 19" panel rack mounting
- Wall mounting
- How to reach the rear side of the IED
- Side-by-side 19" rack mounting
- IED in the 670 series mounted with a RHGS6 case
- Mounting procedure for side-by-side flush mounting
- Influencing factors
- Type tests according to standard
- REX060 Front panel controls
- Coupling capacitor unit REX061
- Shunt resistor unit REX062
- Injection unit REX060 from rear side
- Type tests according to standards
- Section 23 Labels
- Labels on injection equipment
- Section 24 Connection diagrams
- Section 25 Inverse time characteristics
- Principle of operation
- Inverse characteristics
- Section 26 Glossary
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Document symbols and conventions
- Document conventions
- IEC 61850 edition 1 / edition 2 mapping
- Section 2 Application
- Main protection functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 3 Configuration
- Description of configuration B30
- Description of configuration C30
- Section 4 Analog inputs
- Example
- Example 1
- Example 3
- Examples on how to connect, configure and set CT inputs for most commonly used CT connections
- Example on how to connect a star connected three-phase CT set to the IED
- Example how to connect single-phase CT to the IED
- Relationships between setting parameter Base Current, CT rated primary current and minimum pickup of a protection IED
- Setting of voltage channels
- Examples how to connect, configure and set VT inputs for most commonly used VT connections
- Example on how to connect a phase-to-phase connected VT to the IED
- Example on how to connect an open delta VT to the IED for high impedance earthed or unearthed networks
- Example how to connect the open delta VT to the IED for low impedance earthed or solidly earthed power systems
- Example on how to connect a neutral point VT to the IED
- Section 5 Local HMI
- Display
- LEDs
- Keypad
- Local HMI functionality
- Parameter management
- Front communication
- C37.118 Phasor Measurement Data Streaming Protocol Configuration PMUCONF
- Short guidance for use of TCP
- Short guidance for use of UDP
- Protocol reporting via IEEE 1344 and C37.118 PMUREPORT
- Operation principle
- Frequency reporting
- Reporting filters
- Scaling Factors for ANALOGREPORT channels
- PMU Report Function Blocks Connection Rules in PCM600 Application Configuration Tool (ACT)
- Setting guidelines
- Transformer differential protection T2WPDIF and T3WPDIF
- Elimination of zero sequence currents
- Inrush restraint methods
- Cross-blocking between phases
- On-line compensation for on-load tap-changer position
- Open CT detection
- Typical main CT connections for transformer differential protection
- Application Examples
- Summary and conclusions
- High impedance differential protection, single phase HZPDIF
- The basics of the high impedance principle
- Connection examples for high impedance differential protection
- Connections for 1Ph High impedance differential protection HZPDIF
- Settings of protection function
- Tertiary reactor protection
- Restricted earth fault protection
- Alarm level operation
- Generator differential protection GENPDIF
- Application
- Percentage restrained differential operation
- Negative sequence internal/external fault discriminator feature
- Other additional options
- Low impedance restricted earth fault protection REFPDIF
- Transformer winding, solidly earthed
- Transformer winding, earthed through zig-zag earthing transformer
- Autotransformer winding, solidly earthed
- Multi-breaker applications
- CT earthing direction
- Settings
- Full-scheme distance measuring, Mho characteristic ZMHPDIS
- High speed distance protection ZMFPDIS
- Fault infeed from remote end
- Load encroachment
- Short line application
- Long transmission line application
- Tapped line application
- Setting of reverse zone
- Setting of zones for parallel line application
- Setting the reach with respect to load
- Zone reach setting lower than minimum load impedance
- Zone reach setting higher than minimum load impedance
- Other settings
- High speed distance protection for series compensated lines ZMFCPDIS
- Series compensation in power systems
- Increase in power transfer
- Impact of series compensation on protective IED of adjacent lines
- Distance protection
- Underreaching and overreaching schemes
- Setting of zone 1
- Setting of reach in resistive direction
- Load impedance limitation, without load encroachment function
- Parameter setting guidelines
- Pole slip protection PSPPPAM
- Identification
- Setting example for line application
- Setting example for generator application
- Out-of-step protection OOSPPAM
- Loss of excitation LEXPDIS
- Sensitive rotor earth fault protection, injection based ROTIPHIZ
- Rotor earth fault protection function
- Connecting and setting voltage inputs
- Settings for sensitive rotor earth fault protection,ROTIPHIZ
- stator earth fault protection, injection based STTIPHIZ
- Stator earth fault protection function
- stator earth fault protection
- Under impedance protection for generators and transformers ZGVPDIS
- Operating zones
- Zone 1 operation
- Zone 3 operation
- Undervoltage seal-in function
- External block signals
- Under voltage seal-in
- Rotor earth fault protection using CVGAPC
- Instantaneous phase overcurrent protection PHPIOC
- Meshed network with parallel line
- Directional phase overcurrent protection, four steps OC4PTOC
- Settings for each step
- Setting example
- Instantaneous residual overcurrent protection EFPIOC
- Directional residual overcurrent protection, four steps EF4PTOC
- Common settings for all steps
- nd harmonic restrain
- Parallel transformer inrush current logic
- Switch onto fault logic
- Transformer application example
- Four step directional negative phase sequence overcurrent protection NS4PTOC
- Sensitive directional residual overcurrent and power protection SDEPSDE
- Thermal overload protection, two time constants TRPTTR
- Setting guideline
- Breaker failure protection CCRBRF
- Pole discordance protection CCPDSC
- Directional underpower protection GUPPDUP
- Directional overpower protection GOPPDOP
- Negativ sequence time overcurrent protection for machines NS2PTOC
- Features
- Generator continuous unbalance current capability
- Start sensitivity
- Accidental energizing protection for synchronous generator AEGPVOC
- Voltage-restrained time overcurrent protection VRPVOC
- Application possibilities
- Voltage-restrained overcurrent protection for generator and step-up transformer
- Overcurrent protection with undervoltage seal-in
- Two step undervoltage protection UV2PTUV
- Settings for two step undervoltage protection
- Two step overvoltage protection OV2PTOV
- Equipment protection, such as for motors, generators reactors and transformers
- Two step residual overvoltage protection ROV2PTOV
- Stator earth-fault protection based on residual voltage measurement
- Power supply quality
- Direct earthed system
- Settings for two step residual overvoltage protection
- Overexcitation protection OEXPVPH
- Service value report
- Voltage differential protection VDCPTOV
- Underfrequency protection SAPTUF
- Overfrequency protection SAPTOF
- Rate-of-change of frequency protection SAPFRC
- Frequency time accumulation protection function FTAQFVR
- General current and voltage protection CVGAPC
- Current and voltage selection for CVGAPC function
- Base quantities for CVGAPC function
- Inadvertent generator energization
- Negative sequence overcurrent protection
- Generator stator overload protection in accordance with IEC or ANSI standards
- for generators
- Voltage restrained overcurrent protection for generator and step-up transformer
- General settings of the instance
- Setting for UC1
- Setting for UV2
- Multipurpose filter SMAIHPAC
- Current circuit supervision CCSSPVC
- Fuse failure supervision FUFSPVC
- Negative sequence based
- Zero sequence based
- Dead line detection
- Section 15 Control
- Synchrocheck
- Energizing check
- Voltage selection
- External fuse failure
- Single circuit breaker with single busbar
- selection
- Double circuit breaker
- Bay control QCBAY
- Switch controller SCSWI
- Switches SXCBR/SXSWI
- XLNPROXY
- Reservation function (QCRSV and RESIN)
- Interaction between modules
- Bay control (QCBAY)
- Switch (SXCBR/SXSWI)
- Interlocking
- Configuration guidelines
- Signals from bypass busbar
- Signals from bus-coupler
- Configuration setting
- Interlocking for bus-coupler bay ABC_BC
- Interlocking for transformer bay AB_TRAFO
- Interlocking for bus-section breaker A1A2_BS
- Interlocking for bus-section disconnector A1A2_DC
- Signals in double-breaker arrangement
- Signals in 1 1/2 breaker arrangement
- Interlocking for busbar earthing switch BB_ES
- Interlocking for double CB bay DB
- Interlocking for 1 1/2 CB BH
- Voltage control
- TR1ATCC or TR8ATCC Setting group
- TCMYLTC and TCLYLTC general settings
- Logic rotating switch for function selection and LHMI presentation SLGAPC
- Generic communication function for Double Point indication DPGAPC
- AutomationBits, command function for DNP3.0 AUTOBITS
- Tripping logic SMPPTRC
- Three-phase tripping
- Single- and/or three-phase tripping
- Single-, two- or three-phase tripping
- Example of directional data
- Blocking of the function block
- Fixed signal function block FXDSIGN
- Boolean 16 to Integer conversion B16I
- Boolean to integer conversion with logical node representation 16 bit BTIGAPC
- Integer to Boolean 16 conversion IB16
- ITBGAPC
- Pulse integrator TIGAPC
- Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
- Comparator for integer inputs - INTCOMP
- Comparator for real inputs - REALCOMP
- Measurement
- Zero clamping
- Setting examples
- Gas medium supervision SSIMG
- Liquid medium supervision SSIML
- Breaker monitoring SSCBR
- Setting procedure on the IED
- Event function EVENT
- Disturbance report DRPRDRE
- Recording times
- Analog input signals
- Consideration
- Logical signal status report BINSTATREP
- Running hour-meter TEILGAPC
- function (LOL1)
- Pulse-counter logic PCFCNT
- Function for energy calculation and demand handling ETPMMTR
- Access point
- Redundant communication
- Merging unit
- Communication protocols
- Receiving data
- IEC/UCA 61850-9-2LE communication protocol
- Specific settings related to the IEC/UCA 61850-9-2LE communication
- synchronization
- IEC 61850 quality expander QUALEXP
- LON communication protocol
- MULTICMDRCV and MULTICMDSND
- IEC 60870-5-103 communication protocol
- Design
- Settings for RS485 and optical serial communication
- Settings from PCM600
- Function and information types
- DNP3 Communication protocol
- Section 21 Remote communication
- Communication hardware solutions
- Section 22 Security
- Change lock CHNGLCK
- Denial of service SCHLCCH/RCHLCCH
- Section 23 Basic IED functions
- Measured value expander block RANGE_XP
- Signal matrix for binary inputs SMBI
- Test mode functionality TESTMODE
- Process bus IEC/UCA 61850-9-2LE synchronization
- Section 24 Requirements
- Conditions
- Fault current
- Rated equivalent secondary e.m.f. requirements
- Transformer differential protection
- Breaker failure protection
- standards
- Current transformers according to ANSI/IEEE
- SNTP server requirements
- IEC/UCA 61850-9-2LE Merging unit requirements
- Section 25 Glossary
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Related documents
- Document conventions
- IEC 61850 edition 1 / edition 2 mapping
- Section 2 Safety information
- Caution signs
- Note signs
- Section 3 Available functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 4 Starting up
- Checking the power supply
- IED start-up sequence
- Energizing REX060
- Writing an application configuration to the IED
- Checking CT circuits
- Checking VT circuits
- Checking the binary input/output circuits
- Binary output circuits
- Section 5 Configuring the IED and changing settings
- Configuring analog CT inputs
- Section 6 Calibrating injection based sensitive rotor earth fault protection
- Launching injection commissioning tool (ICT)
- Performing calibration
- Acquiring references
- Verifying calibration
- Auditing
- Editing features in graph
- Logging measurements to file
- Section 7 Calibrating injection based 100% stator earth fault protection
- Section 8 Establishing connection and verifying the SPA/IEC communication
- Verifying the communication
- Fibre optic loop
- Section 9 Establishing connection and verifying the LON communication
- The LON Protocol
- Optical budget calculation for serial communication with LON
- Section 10 Establishing connection and verifying the IEC
- Section 11 Establishing connection and verifying the IEEE C37.118/1344 communication
- Setting the PMU station communication (PMU configuration)
- Setting the TCP/UDP client communication
- Verifying the IEEE C37.118/1344 TCP communication
- Verifying the IEEE C37.118/1344 UDP communication
- Optical budget calculation for PMU - PDC communication
- Section 12 Testing IED operation
- Preparing the IED to verify settings
- Activating the test mode
- Connecting the test equipment to the IED
- Releasing the function to be tested
- Verifying analog primary and secondary measurement
- Testing the protection functionality
- Enable forcing by using LHMI
- Forcing by using LHMI
- Forcing by using PCM600
- How to undo forcing changes and return the IED to normal operation
- Testing disturbance report
- Event recorder (ER) and Event list (EL)
- Identifying the function to test in the technical reference manual
- Completing the test
- High impedance differential protection HZPDIF (87)
- Impedance protection
- Measuring the operating limit of set values
- Measuring the operating time of distance protection zones
- Verifying the settings
- Loss of excitation LEXPDIS (40)
- Four step non-directional ground fault protection
- Measuring the trip and time limit for set values
- Checking the re-trip and back-up times
- Verifying the re-trip mode
- Verifying instantaneous back-up trip at CB faulty condition
- Voltage-restrained time overcurrent protection VRPVOC(51V)
- Generator stator overload protection GSPTTR (49S)
- Generator rotor overload protection (49R)
- Two step overvoltage protection OV2PTOV (59)
- Check of voltage differential trip and alarm levels
- Check of trip and trip reset timers
- Stator ground fault protection, 3rd harmonic based STEFPHIZ (59THD)
- Verifying settings
- Built-in overcurrent feature (non-directional)
- Overcurrent feature with voltage restraint
- Over/Undervoltage feature
- Measuring the trip value for the negative sequence function
- Measuring the trip value for the zero-sequence function
- Checking the operation of the dv/dt and di/dt based function
- Testing the synchronizing function
- Testing the synchrocheck functionality
- Testing the energizing check
- Testing the voltage selection
- Tap changer control and supervision TCMYLTC, TCLYLTC
- Secondary test
- Check the normal voltage regulation function
- Check the undervoltage block function
- Check the overcurrent block function
- Parallel voltage regulation
- Logic
- Circuit breaker lockout
- Testing the gas medium supervision for pressure alarm and pressure lockout conditions
- Liquid medium supervision SSIML
- Limit counter L4UFCNT
- Remote communication
- Section 14 Checking the directionality
- Section 15 Commissioning and maintenance of the fault clearing system
- Visual inspection
- Preparation
- Self supervision check
- Measurement of service currents
- Section 16 Troubleshooting
- Fault tracing
- Using front-connected PC
- Diagnosing the IED status via the LHMI hint menu
- Repair instruction
- Repair support
- Section 17 Glossary
Relion REG670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Related documents
- Document conventions
- IEC 61850 edition 1 / edition 2 mapping
- Section 2 Safety information
- Caution signs
- Note signs
- Section 3 Available functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 4 Starting up
- Checking the power supply
- IED start-up sequence
- Setting up communication between PCM600 and the IED
- Writing an application configuration to the IED
- Checking CT circuits
- Checking VT circuits
- Checking the binary input/output circuits
- Checking optical connections
- Section 5 Configuring the IED and changing settings
- Configuring analog CT inputs
- Section 6 Calibrating injection based sensitive rotor earth fault protection
- Launching injection commissioning tool (ICT)
- Performing calibration
- Acquiring references
- Verifying calibration
- Auditing
- Editing features in graph
- Logging measurements to file
- Section 7 Calibrating injection based 100% stator earth fault protection
- Section 8 Establishing connection and verifying the SPA/IEC communication
- Verifying the communication
- Fibre optic loop
- The LON Protocol
- Optical budget calculation for serial communication with LON
- Section 10 Establishing connection and verifying the IEC
- Section 11 Establishing connection and verifying the IEEE C37.118/1344 communication
- Setting the PMU station communication (PMU configuration)
- Setting the TCP/UDP client communication
- Verifying the IEEE C37.118/1344 TCP communication
- Verifying the IEEE C37.118/1344 UDP communication
- Optical budget calculation for PMU - PDC communication
- Section 12 Testing IED operation
- Preparing the IED to verify settings
- Activating the test mode
- Connecting the test equipment to the IED
- Releasing the function to be tested
- Verifying analog primary and secondary measurement
- Testing the protection functionality
- Enable forcing using TESTMODE function block
- Forcing by using PCM600
- operation
- Testing disturbance report
- Event recorder (ER) and Event list (EL)
- Identifying the function to test in the technical reference manual
- Completing the test
- High speed distance protection zones, quadrilateral and mho characteristic ZMFPDIS
- Measuring the operating limit of set values
- Measuring the operating time of distance protection zones
- Verifying the settings
- Loss of excitation LEXPDIS
- Four step non-directional earth fault protection
- Measuring the operate and time limit for set values
- Checking the re-trip and back-up times
- Verifying the back-up trip mode
- Verifying instantaneous back-up trip at CB faulty condition
- Voltage-restrained time overcurrent protection VRPVOC
- Extended testing
- Check of voltage differential trip and alarm levels
- Check of trip and trip reset timers
- Final adjustment of compensation for VT ratio differences
- Testing
- Verifying settings
- Built-in overcurrent feature (non-directional)
- Overcurrent feature with current restraint
- Over/Undervoltage feature
- Measuring the operate value for the negative sequence function
- function
- Testing the synchronizing function
- Testing the energizing check
- Testing the voltage selection
- Apparatus control APC
- Secondary test
- Check the normal voltage regulation function
- Check the undervoltage block function
- Check the overcurrent block function
- Parallel voltage regulation
- ph/3ph operating mode
- ph/2ph/3ph operating mode
- Circuit breaker lockout
- alarm and temperature lock out conditions
- Testing the liquid medium supervision for level alarm and level lockout conditions
- Breaker monitoring SSCBR
- Verifying the signals and settings
- Function for energy calculation and demand handling ETPMMTR
- Remote communication
- Overview
- clearing system
- Visual inspection
- Recording
- Measurement of service currents
- Restoring
- Section 16 Troubleshooting
- Fault tracing
- Using front-connected PC
- Diagnosing the IED status via the LHMI hint menu
- Repair instruction
- Repair support
- Section 17 Glossary
Related products
RELION REL670Relion REC670RELION RET670Relion RES670RELION RER670RELION REB670RelionRelion 670 seriesRELION REM611Relion REB500ABB categories
Industrial Equipment
DC Drives
Controller
Relays
Measuring Instruments
Circuit breakers
Battery Charger
Industrial Electrical
Transformer
Switch
manualsdatabase
Your AI-powered manual search engine