Chapter 6: Using the Web Interface197Button FunctionUpDownBottomRestores to the default sequenceNext time when power cycling the PX3TS, it will turn on all outlets basedon the new outlet order.The new order also applies when performing the power-on orpower-cycling operation on partial outlets.To set a power-on delay for any outlet:1. On the same outlets list, click the 'Delay' column of the outlet thatrequires a wait after it is turned on.2. Type a new value in seconds.3. Click Save.The PX3TS will insert a power-on delay between the configured outletand the one following it during the power-on process.Setting Non-Critical OutletsOutlets that are turned off when load shedding is activated are callednon-critical outlets. Outlets that are not affected by load shedding arecalled critical outlets. SeeLoad Shedding Mode (on page 199).Per default, all outlets are configured as critical.To determine critical and non-critical outlets:1. On the Outlets page, click > Load Shedding Setup.2. To set non-critical outlets, select the checkboxes of those you want.