Chapter 6: Using the Web Interface211 Type a new value in the accompanying text box.For concepts of thresholds, deassertion hysteresis and assertiontimeout, seeSensor Threshold Settings (on page 761).5. Click Save.Individual OCP PagesAn OCP's data/setup page is opened after clicking any OCP's name onthe OCPs or Dashboard page. SeeOCPs (on page 209) orDashboard (onpage 150).General OCP information:Field DescriptionLabel This OCP's physical number.Status open or closed. When an OCP trips (open), if your PX3TSis an outlet-metered model thatsupports "outlet peak current" sensors,a message will show up, indicating whichoutlet is likely to trigger the OCP-trippedevent.Type This OCP's type.Rating This OCP's rated current.Lines Lines associated with this OCP.Protected Outlets Outlets associated with this OCP.