Chapter 8: Using the Command Line Interface610Example - Default Upper Thresholds for TemperatureIt is assumed that your preferred measurement unit for temperature isset to degrees Celsius. Then the following command sets the defaultUpper Warning threshold to 20and Upper Critical threshold to 24for all temperature sensors.config:#defaultThresholds temperature upperWarning 20upperCritical 24Sensor Threshold Configuration CommandsA sensor configuration command begins withsensor. You can use thecommands to configure the threshold, hysteresis and assertion timeoutvalues for any sensor associated with the following items:InletsOutlets (only available for models with outlet switching)Overcurrent protectorsEnvironmental sensorsTransfer switch sensorsIt is permitted to assign a new value to the threshold at any timeregardless of whether the threshold has been enabled.Commands for Inlet SensorsA sensor configuration command for inlets begins withsensor inlet.You can configure various inlet sensor threshold settings at a time bycombining multiple commands. SeeMulti-Command Syntax (on page635).Set the Upper Critical threshold for an inlet sensor:config:#sensor inlet upperCritical Set the Upper Warning threshold for an inlet sensor:config:#sensor inlet upperWarning Set the Lower Critical threshold for an inlet sensor: